FP-PS-4 Operating Instructions
8
ni.com
6. Connect the green or green/yellow conductor into the ground
terminal.
Caution
When you install the conductors, make sure that
the entire conductor is in the screw terminal and that there
are no loose strands outside of the terminal. Only install
one wire in each terminal.
Specifications
The following specifications are typical for a range of 0 to 60 °C,
unless otherwise noted.
Installation
Terminal wiring ................................ 16-26 AWG copper
conductor wire with 7 mm
(0.275 in.) strip length as
shown in Figure 8
Figure 8. Conductor Wire with the Correct Strip Length (drawing is to scale)
Torque for screw terminals ............... 0.5-0.6 Nm (4.4–5.3 in.-lbs)
Input Characteristics
Input voltage ..................................... 90–264 VAC
Frequency ......................................... 47–63 Hz, single phase
Maximum current consumption........ 0.6 A at 120 VAC, 60 Hz
Input protection................................. Nonreplaceable internal
AC fuse
Output Characteristics
Output voltage .................................. 24 VDC, nonadjusting
Nominal current (I
N
) ......................... 600 mA
Nominal continuous power
0 to 50 °C ................................... 15 W
50 to 60 °C ................................. 10 W
7 mm