TM0081      
Page 21 of 51
 Issue 1.01
Figure 23: System Fault
!
 
To review additional system fault information, press enter (
) button.
!
 
The display updates providing additional system fault specific information. Refer to Figure 24.
Figure 24: System fault – Power Supply Fault
Should additional system faults be detected, then the total number of faults counter will increase. The total
number of active system faults will also increase. To view the new system fault information, press the enter (
)
button followed by the scroll button. Refer to Figure 25.
Figure 25: System Fault Number 2 – Loop 01 Fault
6.4.2 
Zone Fault Conditions
Zone faults generally relate to detection loop input type devices such as smoke detectors, heat detectors, break
glass units and the input channel of the input \ output module. These types of devices are programmed during
commissioning to geographical zone numbers located within the installation.
If a zone fault occurs, generally as a result of a faulty loop device:
!
 
The yellow COMMON FAULT light flashes
!
 
An audible buzzer on the panel sounds intermittently
!
 
The event printer prints out the full fault alarm details (when installed and fully enabled)
!
 
The display updates providing the user with the alarm header text, total number of alarms within the
fault priority queue, zone fault information and total number of zone faults present. Refer to Figure
26.
Figure 26: Zone Fault Condition
Note: Figure 26 shows an example of multiple faults – Total number of priority 4 fault conditions is 3, 2 x system
faults and 1 x zone fault.