PLUG IN OPTIONS – INSTALLATION AND COMMISSIONING
12.1
VEGA LOOP CARD - Part Number 44782-K074
Installation
1. 
Ensure that the control panel is powered down. Disconnect the stand-by battery and mains supply.
2. 
Install the 44782-K074 card into the next available fixing plug located on the BLC motherboard card as
shown in Figure 34.
Figure 34: Loop Card Installation
3. 
Secure the card to the earth retaining bar using the single M3 fixing screw.
4. 
Ensure the loop card plug is fully inserted into the motherboard socket.
5. 
Connect the external detection loop cables to the terminals located on the new loop card as shown in
the Figure 6.
6. 
Power up the system. Apply mains supply first followed by the stand-by battery.
Set-up
1. 
Using the panel menu structure, locate the option ‘Loop quantity’. This can be found from the top-level
menu under:
Set → Standard features → Panel setup. Refer Table 10.
2. Increase 
the 
Loop quantity count.
3. 
Using the panel menu structure, locate the option Autolearn. This can be found from the top-level menu
under:
Set→ Loop config→ Autolearn. Refer Table 8.
4. 
Enter the loop number to Autolearn the new detection loop.
5. 
Upon completion of the loop Autolearn process, the panel will indicate a ‘logon fault’
6. 
Using the panel menu structure, locate the option ‘Accept logon count’. This can be found from the top-
level menu under:
Set→Loop config→ Accept logon count. Refer Table 8.
7. 
Check - the correct number of detectors attached to the new loop is recorded at the control panel. This
can be found using the panel menu structure; locate the option Single loop. This can be found from the
top-level menu under:
List→Loop devices→Single loop. Refer Table 7.
Using VIPER
1. 
The control panel is now ready to receive site-specific data.
2. 
Using the upload \ download software application, VIPER, download from the control panel to computer,
the site file information.
3. 
Using the computer, enter all relevant detector location text, zone information and assign any required
cause and effect evacuation strategy.
4. 
Save the site file information before uploading to the control panel.