Setting up Your Morgan 
Wood Fireplace Insert 
U
NPACKING
 
 
HearthStone Stoves packages your Morgan Fireplace 
Insert with the greatest care, so that it ships safely.  Under 
certain circumstances, however, damage can occur during 
transit and handling.  When you receive your Fireplace 
Insert, unpack it carefully, inspecting your Fireplace 
Insert and all parts for damage.  Also, make sure that all 
parts are included in the box.  If any parts are damaged or 
missing, please contact your dealer immediately. 
 
 
I
NSTALLING 
Y
OUR 
F
IREPLACE 
I
NSERT
 
When Installing this unit in a fireplace, you must attach 
the metal label provided (3300-625) to the fireplace prior 
to installing the insert. To install the tag, 
 
Make sure that the Fireplace Insert will have enough 
clearance to combustible materials that would surround 
the insert.  These combustibles can include walls, floor, 
ceiling, fireplace, and chimney.  You must carefully 
consider the clearances to all of these combustibles before 
actually connecting your Fireplace Insert.   
 
Read this chapter to obtain a sound understanding of how 
to properly install your Fireplace Insert. 
 
If you use a close clearance connector pipe, it must be 
tested to UL standards and listed. Check the listing of 
your pipe for actual clearances.  The diagrams in this 
manual represent typical installations, but are specific to 
the Simpson Dura-Vent DVL brand.  Clearances cannot 
be reduced without the use of close clearance connector 
pipe and/or by protecting the surfaces per NFPA 211 
standards.
 
 
 
National Fire Protection Agency 
 Batterymarch 
Park 
 
Quincy, MA  02269 
 1-800-344-3555 
 1-617-770-3000 
 
 
 
 
 
 
 
 
Figure 2 Minimum Fireplace Dimensions 
 
 
H
EARTH 
R
EQUIREMENTS 
A
ND 
F
LOOR 
P
ROTECTION
 
 
Combustible flooring must be protected with a covering 
of noncombustible material (slate, marble tiles, other 
noncombustible material can be used for this purpose). 
The floor protection must extend beyond the body of the 
Fireplace Insert at the minimum as follows and have a 
minimum “R-Value” of 1.0. 
Hearth must be of a 
non-combustible material 
with an "R-Value" of at 
least 1.0
From 
fuel 
door 
opening
 
Figure 3 Hearth Requirements 
 
*   Installations in Canada require 18” (45.72 cm) of floor  
protection in the front. 
HearthStone Quality Home Heating Products, Inc. ®                                                                                                                                                                       Morgan Model 8470            