Справочник Пользователя для Mitsubishi Electronics Mitsubishi Digital Electronics Home Theater Server QnUCPU

Скачать
Страница из 630
6
 
-
 
10
6.4  
Output Mode at Operating Status Change (STOP to
 
RUN)
(1) Definition
When the operating status is changed from RUN to STOP, the CPU module internally stores the 
outputs (Y) in the RUN status and then turns off all the outputs (Y).
The status of the outputs (Y) when the operating status of the CPU module is changed back from 
STOP to RUN can be selected from the following two options in the parameter setting in GX 
Developer.
 • Output the output (Y) status prior to STOP. (“Previous state”)
 • Clear the output (Y) status. (“Recalculate (output is 1 scan later)”)
(2) Application
This function is used to determine the status of outputs (whether to resume the outputs from the 
previous status or not) when the operating status is changed from STOP to RUN in the holding circuit
.
 • When outputting the output (Y) status prior to STOP
 • When clearing the output (Y) status
Figure 6.6 Holding circuit
Figure 6.7 Timing chart when the parameter is set to "Previous state"
Figure 6.8 Timing chart when the parameter is set to "Recalculate (output is 1 scan later)"
Start  
button
Stop  
button
OFF
OFF
ON
ON
OFF
X21
Y0
X20
RUN    STOP
STOP    RUN
OFF
OFF
ON
ON
OFF
X21
Y0
X20
RUN    STOP
STOP    RUN