CHAPTER6 FUNCTIONS
1
2
3
4
5
6
7
8
6.
20 
 S
ys
tem
 Display
 of
 CP
U M
odule wit
h G
X
 Dev
e
lo
per
  
6
 
-
 
113
6.20  System Display of CPU Module with GX Developer
When the CPU module is connected to GX Developer, this function can check the following items of the modules on 
the base unit in the System Monitor screen.
 • Installed status
 • Parameter status
 • Module’s Detailed Information
 • Product information
(1) Installed status
The control CPU, model name, and the number of points of the modules on the selected base unit can be 
checked.
"Unmounting" is displayed in the field of a number of slot where a module is not mounted.
The model name of a module on a slot to which "Empty" is set in the I/O assignment tab of the PLC parameter 
dialog box is not displayed.
When using a redundant base unit, mounted status of the power supply module is also displayed. 
Note1
(2) Parameter status
The I/O number, type, and the number of points of the module on each slot of the selected base unit can be 
displayed.
If the Parameter status displays "0" for an empty slot or assignment error, it indicates that the I/O assignment 
setting of the PLC parameter dialog box and the mounted status differs. Therefore, change the I/O assignment 
setting so that it may match with the mounted status.
When using a redundant base unit, mounted status of the power supply module is also displayed. 
Figure 6.84 System Monitor screen
Note1
(4)
(5)
(6)
(7)
(8)
(9)
(1)
(2)
(3)
Note6.10
Before monitoring the Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q13UDHCPU, or Q26UDHCPU, check 
the versions of the CPU module and GX Developer.(