Справочник Пользователя для Mitsubishi Electronics Mitsubishi Digital Electronics Home Theater Server QnUCPU

Скачать
Страница из 630
App
 
-
 
12
Appendix 3.1.2 Replacing High Performance model QCPU with Universal 
model QCPU
(1)
System configuration
*1: The serial number (first five digits) of the applicable module (Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q13UDHCPU, and 
Q26UDHCPU) must be "10041" or earlier.
TableApp.9 Precautions for replacement and replacement methods (System configuration)
Item
Precautions
Replacement method
Reference
Use of AnS/A series 
module
AnS/A series modules are not supported.
Use Q series modules.
---
GOT
GOT900 series cannot be connected.
Use GOT1000 series.
---
Programming tool 
connection
Applicable USB cables are different.
• High Performance model QCPU
... A-B type
• Universal model QCPU
... A-miniB type
Use USB cables of A-miniB type. Or, use 
USB conversion adapters of B-miniB 
type.
---
Applicable products 
and software
Products and softwares compatible with 
the Universal model QCPU must be used.
Products need to be replaced for the 
compatibility with the Universal model 
QCPU and software need to be upgraded 
for the communication with the Universal 
model QCPU are described in Appendix 
3.2
.
Multiple CPU system
To configure a multiple CPU system, CPU 
modules compatible with the Universal 
model QCPU must be used.
CPU modules compatible with the 
Universal model QCPU are described in 
Appendix 3.2.
In a multiple CPU system using the 
Motion CPU, an existing auto refresh area 
and user setting area cannot be used for 
data communication with the Motion CPU.
For data communication with the Motion 
CPU, use an auto refresh area and user 
setting area in the multiple CPU high-
speed transmission area.
Chapter 4 in the QCPU 
User's Manual (Multiple 
CPU System)
Redundant power 
supply system
*1
In a redundant power supply system 
using the Q38RB redundant power supply 
main base unit and the Q68RB redundant 
power supply extension base unit, the 
status of the power supply module cannot 
be stored in the special relay and special 
register (SM1780 to SM1783/SD1780 to 
SD1783). The status cannot be displayed 
on the system monitor screen.
Check the status of the power supply 
module by the LED on the front of the 
module.
Section 5.3  in the 
QCPU User's Manual 
(Hardware Design, 
Maintenance and 
Inspection)
MELSECNET/H
The simple dual-structured network 
function is not supported.
---
Section 7.7 in the Q 
Corresponding 
MELSECNET/H 
Network System 
Reference Manual (PLC 
to PLC network)