Справочник Пользователя для Mitsubishi Electronics Mitsubishi Digital Electronics Electronic Accessory Q02CPU

Скачать
Страница из 236
 
 
 
App - 2                                                                                                                                                   App - 2 
MELSEC-Q
 
APPENDICES 
 
APPENDIX 1.2 Description of the errors of the error codes (4000
H
 to 4FFF
H
The error contents of the error codes (4000
H
 to 4FFF
H
) detected by the CPU module 
and the messages displayed by the GX Developer are shown below. 
 
Error code 
(hexadecimal) 
Error 
item 
Error description 
Countermeasure 
4000
H
 
Sum check error 
Check the connection status of the connection cable 
with the CPU module 
4001
H
 
Remote request that is not handled was 
executed. 
Check the requested remote operation. 
4002
H
 
4003
H
 
Command for which a global request cannot be 
performed was executed. 
Check the requested command. 
4004
H
 
CPU module cannot execute the request 
contents because it is in system protect 
Turn off the CPU module system protect switch. 
4005
H
 
The volume of data handled according to the 
specified request is too large. 
Reduce the volume of data to that which can be 
processed at the specified request. 
4006
H
 
The password cannot be deleted. 
Delete the set password. 
4008
H
 
CPU 
related 
error 
The CPU module is not BUSY (The buffer is not 
vacant). 
After the free time has passed, reexecute the request. 
4010
H
 
The CPU module is running to the request 
contents cannot be executed. 
Execute after setting the CPU module to STOP status. 
4011
H
 
CPU mode 
error 
The CPU module is not in the STEP-RUN 
status so the request contents cannot be 
executed. 
Execute after setting the CPU module to STEP-RUN 
status. 
 
 
 
 
App