Pressure Systems, Inc.                                                                                        Model 9116 User’s Manual 
 
 
 
Page 59 
 
www.PressureSystems.com 
 
bbbb (hex) 
data selected for inclusion in each stream packet 
0001 ** 
Enable Valve Position Status (reserved for future use) 
0002 Enable DH Temperature Status (see bit map below) 
0010 Enable Pressure EU Data (default if “05” never executed after “00”) 
0020 Enable Pressure A/D Counts 
0040 Enable Pressure Voltages 
0080 Enable DH Temperature EU Data (degrees C) 
0100 Enable DH Temperature A/D Counts 
0200 Enable DH Temperature Voltages 
 
Any DH Temperature Status datum is delivered as a two-byte binary bit map (16-bit, big 
endian) with each bit representing the status of DH #16 through DH #1 respectively.  A bit value 
of 0 (zero) indicates the DH is operating within its specified limits.  A value of 1 (one) indicates 
the DH is outside its specified limits. 
 
Bit 
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 
Chan # 
16 15 14 13 12 11 10 9  8  7  6  5  4  3  2  1 
Binary  1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 
Hex 
8 0 0 1 
 
The above example indicates that Channels 1 and 16 are operating outside the specified 
temperature limits. 
 
Note
 
** This status field (0001) cannot be specified for Model 9116. 
However it is shown should the capability be added to future 
firmware versions. Currently, only Models 9816 and 903x can return 
Valve Position status in their streams.