a) Measurements made differentially to eliminate common-mode noise 
b) Ground lead length of oscilloscope probe shall be ≤ 0.25 inch. 
c) Measurements made where the cable connectors attach to the load. 
d) Outputs bypassed at the point of measurement with a parallel combination of 
10uF tantalum capacitor in parallel with a 0.1uF ceramic capacitors. 
e) Oscilloscope bandwidth of 0 Hz to 20MHz. 
f) Measurements measured at locations where remote sense wires are connected. 
g) Regulation tolerance shall include temperature change, warm up drift and dynamic load 
3.3 Timing Requirements   
These are the timing requirements for the power assembly operation. The output voltages must rise 
from 10% to within regulation limits (T
vout_rise
) within 5 to 70mS. The +5V, +3.3V and +12V output 
voltages should start to rise at about the same time. All outputs must rise monotonically. The +5V 
output needs to be greater than the +3.3V output during any point of the voltage rise. The +5V output 
must never be greater than the +3.3V output by more than 2.25V. Each output voltage shall reach 
regulation within 50 mS (T
vout_on
) of each other during turn on of the power supply. Each output voltage 
shall fall out of regulation within 400 mS (T
vout_off
) of each other during turn off. Figure 1 and figure 2 
show the turn On and turn Off timing requirement. In Figure 2, the timing is shown with both AC and 
PSON# controlling the On/Off of the power supply.     
 
s
ti
n
U
 
 
X
A
M
 
N
I
M
 
n
o
it
p
ir
c
s
e
D
 
m
e
tI
T
v
out_rise
 
  Output  voltage  rise  time  from  each  main  output.(+5Vsb  < 
70mS)
70 
mS 
T
vout_on
 
  All  main  output  must  be  within  regulation  of  each  other 
within this time. 
 
50 
mS 
T
vout_off
 
All main output must leave regulation within this time 
 
400 
mS 
Table 4 – Output Voltage Timing