Справочник Пользователя для IBM Partner Pavilion DS4100

Скачать
Страница из 180
Table
 
10.
 
IBM
 
TotalStorage
 
DS4100
 
AC
 
power
 
requirements
 
Low
 
Range
 
High
 
Range
 
Nominal
 
Voltage
 
90
 
to
 
136
 
VAC
 
180
 
to
 
264
 
VAC
 
Frequency
 
50
 
to
 
60
 
Hz
 
50
 
to
 
60
 
Hz
 
Idle
 
Current
 
2.50
 
A
a
 
1.33
 
A
b
 
Maximum
 
Operating
 
Current
 
3.01
 
A
a
 
1.57
 
A
b
 
a.
 
Typical
 
voltage:
 
115
 
V
 
AC,
 
60
 
Hz
 
at
 
77%
 
power-supply
 
efficiency
 
and
 
0.96
 
power
 
factor
 
b.
 
Typical
 
voltage:
 
230
 
V
 
AC,
 
60
 
Hz
 
at
 
77%
 
power-supply
 
efficiency
 
and
 
0.96
 
power
 
factor
  
Heat
 
output,
 
airflow,
 
and
 
cooling
 
The
 
maximum
 
heat
 
output
 
of
 
the
 
DS4100
 
is
 
390
 
watts
 
(1235
 
BTU/hr).
 
Each
 
DS4100
 
rack-mounted
 
unit
 
requires
 
an
 
airflow
 
of
 
2.5
 
m
3
 
(87
 
ft
3
)
 
per
 
minute.
 
The
 
input
 
air
 
temperature
 
to
 
all
 
rack
 
cabinets
 
should
 
be
 
in
 
the
 
range
 
10°
 
C
 
-
 
35°
 
C
 
(50°
 
F
 
-
 
95°
 
F).
 
The
 
recommended
 
operating
 
temperature
 
is
 
22°
 
C
 
(72°
 
F).
 
When
 
rack
 
cabinets
 
that
 
contain
 
many
 
DS4100s
 
are
 
to
 
be
 
installed
 
together,
 
the
 
following
 
requirements
 
must
 
be
 
met
 
to
 
ensure
 
that
 
the
 
DS4100s
 
are
 
adequately
 
cooled:
 
v
   
Air
 
enters
 
at
 
the
 
front
 
of
 
the
 
rack
 
cabinet
 
and
 
leaves
 
at
 
the
 
back.
 
To
 
prevent
 
the
 
air
 
that
 
is
 
leaving
 
the
 
rack
 
cabinet
 
from
 
entering
 
the
 
intake
 
of
 
another
 
piece
 
of
 
equipment,
 
you
 
must
 
position
 
the
 
rack
 
cabinets
 
in
 
alternate
 
rows,
 
back-to-back
 
and
 
front-to-front.
 
This
 
arrangement
 
is
 
known
 
as
 
“cold
 
aisle/hot
 
aisle”
 
and
 
is
 
shown
 
in
 
 
v
   
Where
 
rack
 
cabinets
 
are
 
in
 
rows,
 
each
 
rack
 
cabinet
 
must
 
touch
 
the
 
rack
 
cabinet
 
that
 
is
 
next
 
to
 
it
 
to
 
reduce
 
the
 
amount
 
of
 
hot
 
air
 
that
 
can
 
flow
 
around
 
from
 
the
 
back
 
of
 
the
 
rack
 
into
 
the
 
intakes
 
of
 
the
 
storage
 
servers
 
that
 
are
 
in
 
that
 
rack
 
cabinet.
 
You
 
should
 
use
 
Suite
 
Attach
 
Kits
 
to
 
completely
 
seal
 
any
 
gaps
 
that
 
remain
 
between
 
the
 
rack
 
cabinets.
 
For
 
details
 
about
 
Suite
 
Attach
 
Kits,
 
contact
 
your
 
marketing
 
representative.
 
v
   
Where
 
rack
 
cabinets
 
are
 
in
 
rows
 
front-to-front
 
or
 
back-to-back,
 
a
 
gap
 
of
 
at
 
least
 
1220
 
mm
 
(48
 
in.)
 
must
 
separate
 
the
 
rows
 
across
 
the
 
cold
 
aisle.
 
v
   
To
 
ensure
 
correct
 
airflow
 
in
 
each
 
rack
 
cabinet,
 
the
 
rack
 
filler
 
plates
 
must
 
be
 
installed
 
in
 
unused
 
positions.
 
Also,
 
all
 
the
 
gaps
 
in
 
the
 
front
 
of
 
the
 
rack
 
cabinets
 
must
 
be
 
sealed,
 
including
 
the
 
gaps
 
between
 
the
 
storage
 
servers.
 
 
 
Chapter
 
1.
 
Introduction
 
15