Справочник Пользователя для HP Performance Optimized Data Center (POD) 40c
Environmental control system 36
Heat exchanger temperature sensors
There are two contact temperature sensors per heat exchanger. One temperature sensor is located on the
inlet supply piping and one temperature sensor is located on the outlet return piping. These sensors measure
There are two contact temperature sensors per heat exchanger. One temperature sensor is located on the
inlet supply piping and one temperature sensor is located on the outlet return piping. These sensors measure
water temperature and report data to the ECS.
Top view shown
Top view shown
Facility connections to ECS
) or
cables that are hard-wired through the two 5.08 cm (2 in) portals on the roof of the utility end of the HP POD
40c G2. The system uses Modbus TCP/IP for communication.
Connecting to the ECS
To connect the network to the ECS control panel, route an Ethernet cable to the appropriate RJ45 connector
End view shown