Environmental control system  50 
The Advanced System Configuration screen displays the static IP address for each power meter, fan controls, 
and other details about the HP POD 40c G2. 
 
Perform the following tasks on this screen: 
 
Configure the IP address for each power meter 
 
Control the fans in each zone 
 
Control the valve 
 
Configure the HP POD 40c G2 serial number 
 
Configure the switchboard serial number 
 
Calibrate the flowmeter 
 
Calibrate the chilled water and differential pressure sensors 
 
Enable or disable power measurement 
You must select Save to store the parameter changes in the system configuration file. If you do not save your 
changes, the old parameters stored in the configuration file reload when the system starts. 
  
 
CAUTION: 
 Making changes to the ECS in the service-level area can cause the cooling system 
components to fail. Only allow authorized, qualified, and trained personnel to change 
configuration settings in the service-level area of the ECS.