Справочник Пользователя для HP Performance Optimized Data Center (POD) 40c

Скачать
Страница из 84
 
Maintenance  74 
Maintenance 
Periodic maintenance 
Perform periodic inspections to ensure that the HP POD 40c G2 continues to perform according to design 
parameters. During periodic inspections, pay special attention to electrical connections and wiring. 
For more specific maintenance information, see the HP Performance Optimized Datacenter 40c G2 
Maintenance and Service Guide
 
Sample HP POD 40c G2 maintenance schedule 
For detailed maintenance information and schedules, consult with HP services. 
The following table is a sample maintenance schedule for an HP POD 40c G2. For more detailed 
maintenance information, see the HP Performance Optimized Datacenter 40c G2 Maintenance and Service 
Guide
 
Component to be inspected 
Frequency 
Electrical connections and wiring—Visual 
Every 30 days 
Electrical connections and wiring—Thermal scans 
Every 180 days 
Condensation and drainage system (leaks)—Visual 
Every 30 days 
Condensation and drainage system (leaks)—Functional 
Every 90 days 
Busway interconnects (tightened) 
Every 180 days 
EPO system 
Every 180 days 
Third-party OEM components (fire alarm and suppression system, humidifier, 
and so on) 
For more information about the 
components, see the Operation 
and Maintenance manual for 
the HP Performance Optimized 
Datacenter 40c G2