Справочник Пользователя для HP Performance Optimized Data Center (POD) 40c
Maintenance 74
Maintenance
Periodic maintenance
Perform periodic inspections to ensure that the HP POD 40c G2 continues to perform according to design
parameters. During periodic inspections, pay special attention to electrical connections and wiring.
For more specific maintenance information, see the HP Performance Optimized Datacenter 40c G2
parameters. During periodic inspections, pay special attention to electrical connections and wiring.
For more specific maintenance information, see the HP Performance Optimized Datacenter 40c G2
Maintenance and Service Guide.
Sample HP POD 40c G2 maintenance schedule
For detailed maintenance information and schedules, consult with HP services.
The following table is a sample maintenance schedule for an HP POD 40c G2. For more detailed
The following table is a sample maintenance schedule for an HP POD 40c G2. For more detailed
maintenance information, see the HP Performance Optimized Datacenter 40c G2 Maintenance and Service
Guide.
Component to be inspected
Frequency
Electrical connections and wiring—Visual
Every 30 days
Electrical connections and wiring—Thermal scans
Every 180 days
Condensation and drainage system (leaks)—Visual
Every 30 days
Condensation and drainage system (leaks)—Functional
Every 90 days
Busway interconnects (tightened)
Every 180 days
EPO system
Every 180 days
Third-party OEM components (fire alarm and suppression system, humidifier,
and so on)
and so on)
For more information about the
components, see the Operation
and Maintenance manual for
and Maintenance manual for
the HP Performance Optimized
Datacenter 40c G2.