Life safety systems  23 
 
Trouble status LED 
 
Input status LED 
 
Output status LED 
 
Acknowledge button 
 
Alarm Silence button 
 
System Reset button 
The fire system and panel are tested by the local certified fire system supplier and witnessed and certified by 
the local Authorities or fire marshal. 
The fire system operator panel requires regular maintenance and service. For more information on the fire 
system operator panel component, see the Operation and Maintenance Manual for the HP Performance 
Optimized Datacenter 20c
 
Fire suppression sequence of operations 
There are two initiation sequences for the fire suppression system, automatic (VESDA) initiation and manual 
initiation. The fire strobe light is activated by either initiation sequence.   
Personnel can determine the status of the system by the differences of the alarm horn. The following table 
describes the fire suppression system status. 
 
Fire suppression 
system stages 
Beats per minute 
Description 
Personnel actions 
Warning 
20 
An alarm condition exists 
Personnel may investigate 
Pre-discharge 
120 
Countdown to fire suppression 
agent has started 
Personnel should evacuate 
Post-discharge 
Steady 
Fire suppression agent is released  Personnel should not enter, 
contact local Authorities 
The fire system operator panel indicates which initiation sequence has begun with indicator lights and a 
panel alarm. These signals are also available to the site BMS system, if connected. 
After the fire suppression system is activated by a VESDA signal or a manual fire button, a 60-second 
countdown begins before the fire suppression agent is released to the HP POD 20c interior through the fire 
suppression system piping. 
VESDA initiation 
The VESDA fire suppression system signal has two levels that the system cycles through when smoke is 
detected. 
 
Level 1—Indicates that the potential for a fire is present. The strobes are illuminated and the horns are 
in the Warning stage. A fire has not yet been detected and personnel may investigate to determine if 
there is a potential for a fire or if a false indication has occurred. 
 
Level 2—Indicates that fire does exist. VESDA Level 1 has already have been reached, the strobes 
illuminate, and the horn progresses to the Pre-discharge stage. A 60-second countdown to fire 
suppression agent release begins and personnel should evacuate immediately. 
Press the fire suppression abort button to interrupt the fire suppression release countdown. Pressing the abort 
button resets the countdown to 10 seconds, regardless of the amount of time elapsed from the original 
60-second countdown. The abort button can be pressed multiple times to reset the fire suppression release