Справочник Пользователя для HP Performance Optimized Data Center (POD) 20cp
Environmental control system 38
Facility chilled water sensors
Five sensors are located on the facility chilled water supply and return pipes. These sensors report data to the
ECS.
Item
Component
Description
1
Return water flow sensor
Detects the water flow rate for the chilled water return
2
Supply water pressure sensor
Detects the water pressure for the chilled water supply
3
Return water pressure sensor
Detects the water pressure for the chilled water return
4
Supply water temperature sensor Detects the water temperature for the chilled water supply
5
Return water temperature sensor Detects the water temperature for the chilled water return
Facility connections to ECS
) or cables that
are hard-wired through the connection portals on the cargo end of the HP POD 20c. The system uses Modbus
TCP/IP for communication.
Connecting to the ECS
To connect the network to the ECS control panel, route an Ethernet cable to the appropriate RJ45 connector