Site requirements  15 
Transformers and switchboards 
The input power for the Critical IT Loads requires a source of 380-415V, 3phase wye power. If it does not 
already exist at the source, you might have to obtain custom transformers to derive this power. In addition to 
the overall loading and KVA size, you must consider the Harmonic Content of the installation when 
specifying the K-Factor of the transformers. Alternatively, you can use Harmonic Mitigating Transformers to 
passively cancel the harmonics generated by the IT equipment. 
HP offers several power solutions that include automatic transfer switching, UPS backup, transformers and 
output distribution switchboards to supply your power needs. 
On-site connections might include: 
 
Main facility power to the primary side of the transformer 
 
Transformer to the switchboard 
 
Switchboard assembly to the HP POD 240e NA 
For connection information, see the HP Site Preparation Drawing Package (on page 
).