Справочник Пользователя для Honeywell Home Theater Server T755U

Скачать
Страница из 40
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—09
2
Temperature Sensors
a
 
(Sensor A or B)
The controller accepts 1,097 Ohms PTC at 77°F (25°C):
• 50021579-001 – Standard sensor (included with all 
models except NEMA 4X models)
• T775-SENS-WR – Water resistant with 5 foot leads 
(included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031D2003 – 5 inch immersion sensor with wiring 
box (use immersion well; P/N 50001774-001)
• C7031J2009 – 12 foot duct averaging sensor with 
wiring box
• C7046D1008 – 8 inch duct probe with mounting flange
• C7100D1001 – 12 inch fast response, duct averaging 
sensor with flange
• C7130B1009 – Room mount sensor
Differential Pressure Sensors
(Sensor A only)
P7640A and PWT pressure transducer models with 
selectable pressure ranges can be used.
The controller accepts pressure sensors with a signal 
output of 0-10 Vdc or 4-20 mA for any output range within 
the following ranges (the minimum and maximum for the 
sensor output range can be adjusted within the following 
limits):
• -500 to 500 PSI
• -30.0 to 30.0 inches w.c.
• -3,000 to 3,000 Pa
• -3,000 to 3,000 kPa
Humidity Sensors
 
(Sensor A only)
The controller accepts 0-10 Vdc or 4-20 mA input with a 
range of 0-100%.
H7625, H7635, and H7655 models (available in 2, 3, and 
5% RH accuracy) can be used.
CO
2
 Sensors
The controller accepts a 0-10 Vdc or 4-20 mA input from 
C7232 and C7632 CO
2
 sensors and is settable in PPM 
units.
Universal Sensors 
(Sensor A only)
The controller accepts 0-5 Vdc, 0-10 Vdc or 4-20 mA input 
for temperature, pressure, humidity CO
2
, etc. They may 
be programmed in units of °F, °C, %, Pa, kPa, PSI, In 
W.C., PPM, or may be unitless (none).
The PPM range is 0 to 9990. 
Choosing none for units, results in no units being 
displayed on the home screen. If no unit is specified the 
range is -9999 to +9999.
Actuators
For more information on compatible actuators or other 
Honeywell products, such as dampers and valves, go to 
www.customer.honeywell.com. From the home page 
select 
Product Selection Tool under Products.
• Spring return models: ML6425, ML7425, MS4105, 
MS4110, MS4120, MS7505, MS7510, MS7520, 
MS8105, MS8110, MS8120
• Non-spring return models: ML4161, ML6174, ML7161, 
MN6105, MN1010, MN7505, ML7164, MN8810
Accessories
• 107324A – Bulb Holder, duct insertion
• 107408 – Heat Conductive Compound, 4 ounce
• 50001774-001 – Immersion Well, stainless steel 304, 
1/2 in. threading
Product Changes
Below are the changes to T775U models starting with 
Series 3 (March 2009). Series 3 can be identified by the 
sideways 3 after the part number on the device label.
1. Setpoint and Enable options added to the DI 
options.
2. 0-5 Vdc sensor inputs are now available (for both 
models).
3. MIN ON time added.
4. HIDE option added to MOD1 and MOD2 (to hide 
them on the home screen).
5. PPM and None added to sensors’ unit of measure.
6. With the new T775U2016 model, all outputs can be 
controlled to Sensor A or Sensor B. The 
T775U2006 model controls only to Sensor A.
a
See form 62-0265 – Temperature Sensors for the T775 
Series 2000 Stand-alone Controller