T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
29
62-0255—09
2.2. Program Next Output 
(Modulating 
Output or Relay)
For the next output, select the desired MOD or Relay from 
the Program menu (see Fig. 58 on page 27).
programming.
When you finish programming the outputs, continue with 
1.3. Exit Programming without Reset
Press the 
HOME button to leave programming mode and 
return to the home screen.
This completes the programming procedure for controllers 
that do not use Reset.
3. PROGRAMMING OUTPUTS 
(MOD AND RELAY) WITH 
RESET
The T775U can be programmed for Reset or No Reset for 
each output. From the factory, the T775U is programmed 
for No Reset. This section describes the steps necessary 
to program the controller for Reset.
To use the Reset feature, the first output (MOD 1) must be 
set to Reset=YES in Setup mode (see “3.1. Setting Up the 
NOTE: Even if the MOD outputs are not used, both 
MOD 1 and MOD 2 must be set to Reset in 
order to configure Reset for the relay(s).
The reset curve established when programming the first 
output (MOD 1) is then used for 
all subsequent outputs 
that are configured for Reset, and each of those outputs 
will be offset from this curve. 
For all outputs that will follow a reset curve, be sure to 
configure for Reset=YES in the setup mode. Choose 
Reset YES or NO for all other outputs you wish to reset, 
then press the 
HOME button to record your selection.
 
Fig. 65. Reset Setup.
NOTE: The first output, Mod 1, must be set for Reset 
to enable the controller’s Reset function.
3.1. Setting Up the Controller for Reset
1. Press and hold the MENU button for five seconds to 
enter Setup mode. 
2. Then choose:
OUTPUTS u
MOD1 u
RESET u
then select YES-BOILER or YES-OTHER (Fig. 65).
You can now press the 
HOME button to exit Setup mode 
Determining and Setting the Reset 
Values
NOTE: When using the Reset feature, Sensor A must 
be sensing the controlled temperature (e.g. 
Boiler), Sensor B must be sensing the reset-
ting temperature (e.g. outdoor temp).
To program an output for Reset, refer to the values as 
shown in the examples below. Choose your own 
appropriate values for Sensor A maximum and minimum 
and Sensor B maximum and minimum.
Reset Example: 
• Sensor A is the boiler sensor and Sensor B is the 
outdoor sensor.
• Maximum boiler temperature desired is 210°F when 
the outdoor temperature is 20°F.
• Minimum boiler temperature desired is 160°F when the 
outdoor temperature is 70°F.
• With the above settings example, when the outdoor 
temperature is 50°F, the effective setpoint is 180°F.
Setback (optional) Example: 
• Setback of -10°F is used to drop the temperature at 
night by 10°F.
• With the above settings example, when the outdoor 
temperature is 50°F, the effective setback setpoint is 
170°F (180°F setpoint minus the 10°F setback). 
NOTE: A single reset curve is programmed for the 
MOD 1 output and is used by all outputs 
setup with RESET=YES.
SETUP
 OUTPUTS
 
 
MOD 1
 
 
 
RESET
SETUP
OUTPUTS
MOD 1
RESET
USE RESET
FOR
MOD 1
YES-BOILER
YES-OTHER
NO