R7140G,L,M BURNER CONTROL MODULES
5
66-1153—03
a
 
The R7140 must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth 
ground wire must be capable of conducting the current to blow the 15A fast blow fuse (or breaker) in the event of an internal short 
circuit. The R7140 needs a low impedance ground connection to the equipment frame, which, in turn, needs a low impedance 
connection to earth ground.
Table 3. Terminal Ratings.
Terminal No.
Description
Ratings
G
Flame Sensor Earth Ground
a
Earth G
Earth Ground
a
L2(N)
Line Voltage Common
L1
Line Voltage Supply (L1)
120 Vac (+10/-15%), 50 or 60 Hz (±10%).
3
Lockout/Running Interlock
120 Vac, 8A run, 43A inrush.
4
Pre-Ignition Interlock Input
120 Vac, 1 mA.
5
Pilot Valve/Ignition
120 Vac. See Table 4.
6
Interrupted/Intermittent Pilot Valve/First Stage Oil Valve 120 Vac. See Table 4.
7
Main Fuel Valve
120 Vac. See Table 4.
8
Burner Motor
120 Vac, 9.8 AFL, 58.8 ALR (inrush).
9
Alarm
120 Vac, 1A pilot duty.
10
Firing Rate High Fire
120 Vac, 75 VA pilot duty.
11
Firing Rate Common
120 Vac, 75 VA pilot duty.
12
Firing Rate Modulate
120 Vac, 75 VA pilot duty.
13
Low Fire Switch Input
120 Vac, 1 mA.
14
Firing Rate Low Fire
120 Vac, 75 VA pilot duty.
15
High Fire Switch Input
120 Vac, 1 mA.
16
Burner Controller and Limits
120 Vac, 1 mA.
17
Shutter
120 Vac, 0.5A.
18
Ignition
120 Vac,
 
4.5A ignition.
F
Flame Sensor
60 to 220 Vac, current limited.
Table 4. Terminal Ratings.
Terminal
Typical Load
Maximum Rating at 120 Vac, 60 Hz
5 or 6
Ignition
Transformer/Pilot
Valve/First Stage Fuel Valve
4.5A ignition and 50 VA pilot duty, or
2.5A ignition and 75 VA pilot duty.
7
Main Fuel Valve(s) (solenoid/
motorized/diaphragm) and 
Vent Valve, if required
250 VA pilot duty or 65 VA pilot duty in parallel with motorized valve(s) using a total of 
1150 VA locked rotor (inrush), 460 VA to open, and 250 VA to hold or motorized valve(s) 
using a total of 1500 VA locked rotor (inrush), 600 VA to open, and 250 VA to hold.