SPECIFICATION DATA
63-1332-02
TR21-WS, TR23-WS, TR21-WK, 
TR23-WK, WRECVR
The WRECVR receiver and TR21-WS, TR23-WS, TR21-WK, 
and TR23-WK are a family of wireless wall modules and 
receiver for use with: 
— Spyder Unitary Controllers: PUL, PVL, etc.
— Excel 10 W7750, W7751, W7752, and W7753 
controllers
— T7350, T7351, and TB8575 low-voltage SuitePRO™  
thermostats
— Will not work with TB7220, TB8220 or TB line voltage 
thermostats, XL15s, W7762, W7763 or certain other 
XL controllers, 
— Will work with WEBs-AX™ I/O Module products if 
using a separate transformer
— Compatibility with various other non-Honeywell con-
trollers that accept 10K type2 NTC temperature inputs
FEATURES
• Wall module to Receiver (point to point) wireless kits 
can replace any standard wired sensor
• Wireless Kits (wall module and receiver) are pre-bound 
at the factory for quick installation
• Signal Strength LED built into the wall module
• Low battery indication
• Optional dip switches available to bind any wall 
module to any receiver
• Approximate 5 year battery life with AA Alkaline 
(included), 7.5 year with Lithium
• Locking screw discourages tampering and battery 
theft.
SPECIFICATIONS
Models:
TR21-WK: Kit (TR21 and WRECVR bound at factory)
TR23-WK: Kit (TR23 and WRECVR bound at factory)
Replacements:
TR21-WS: Wireless Temperature sensor
TR23-WS: WirelessTemperature sensor, with Setpoint Knobs 
(°F, °C, and Relative [warmer to cooler]), O/R Button, and 
LED
WRECVR: Receiver
Environmental Ratings:
• Wall Module Operating Temperature: 45° to 99°F (7° to 
37°C).
• Receiver Operating Temperature: -40° to 150°F (-40° to 
65.5°C).
• Storage Temperature: -40° to 150°F (-40° to 65.5°C).
• Operating Humidity: 5% to 95% RH (non-condensing)
Dimensions: See Fig. 1 and 2.
Accuracy: +/- 1ºF (+/- 0.5ºC) across 12ºC to 30ºC
Setpoint Range for TR23: 56° to 84°F (13° to 29°C)
Accessories: 50007298-001 (pack of 12) medium, cover 
plate; 6-7/8 x 5 in. (175 x 127 mm).
Power:
Receiver Voltage: 20 – 30VAC/DC, 50/60Hz; 24VAC typical
Housing: 
Wall Module: UL94-HB, Receiver: UL94-5VA
Radio Frequency 2.4 GHz (IEEE Std 802.15.4-2003 
compliant)
• Open Range: 3000 feet
• Typical Range: 100 feet
• Output power: 16dBm
• Receiver power consumption: <1.5VA @ 24VAC
• Approximate battery life under normal operating 
conditions:
• 5 years with two AA Alkaline batteries (included)
• 7.5 years with two AA Lithium Batteries 
Transmission interval: 30 seconds
Pressing override button or signal strength button will force an 
immediate transmission.
Approvals:
 This device complies with Part 15 of the FCC rules. Operation 
is subject to the following two conditions:
1) this device may not cause harmful interference, and
2) this device must accept any interference received, 
including interference that may cause undesired operation.
General Rules for Installing Wireless 
Wall Modules
Communication between the wall module and receiver can be 
influenced by a number of factors. Type and thickness of 
building materials and the way in which they are oriented in 
relation to the wall module and receiver will affect 
communication.
Do not place either the wall module or receiver inside metal 
cabinets or enclosures.Try to orient the wall module and 
receiver so that if they are separated by a wall(s), the direction 
of signal travel is as perpendicular to the wall(s) as possible. 
This reduces the effective wall thickness.
When mounting the receiver on a metal duct, stronger 
communication is possible if the wall module is on the same 
side of the duct so the signal doesn’t need to travel through 
the metal duct.
Reduce as much as possible the amount of metal (ducts, file 
cabinets, etc.) between the sensor and the wall module.
Standard drywall (gypsum board) does not greatly affect 
signal strength.