Heat & Glo  •  6000TR-OAK, 6000TR-OAK-IPI  •  383-901  Rev. K  •   5/06
13
Framing  should  be
constructed of 2 X 4
lumber or heavier.
A. ............. 42”*
B. ......... 38 1/2”
C. ............... 22”
D. ......... 42 3/4”
E. ......... 27 7/8”
Figure 3. Framing Dimensions
Step 2.  Framing the Fireplace
Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.
1/2” CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE
0” CLEARANCE TO
FRAMING MEMBER
0” CLEARANCE
1/2” CLEARANCE
FROM BOTH SIDES
OF FIREPLACE
TO COMBUSTIBLE
FRAMING
MEMBER
Shows  center  of  10”  x  12”  vent  framing
holes for top and rear venting. The center
of the hole is one (1) inch (25.4mm) above
the center of the horizontal vent pipe.
E
D
A
B
C
WALL
STUD
3 1/2”
3
Noncombustible  zone  is  defined
by 3” above the elbow for the
entire width and depth (behind
the front header) of the firebox.