Rack System Precautions
The following safety requirements must be considered when the unit is mounted in a rack. 
• The rack design should incorporate stabilizing features suitable to prevent the rack from tipping or 
being pushed over during installation or in normal use.
• When loading a rack with the units, fill the rack from the bottom up and empty from the top down.
• The rack should comply with the airflow requirements detailed in the technical specification.
• The rack design should take into consideration the maximum operating ambient temperature for the 
unit, which is 40°C when dual cooling modules are fitted.
• The rack should have a safe electrical distribution system. it must provide overcurrent protection for 
the unit and must not be overloaded by the total number of units installed in the rack. Consideration 
of the electrical power consumption rating shown on the nameplate should be used when 
addressing these concerns.
• The electrical distribution system must provide a reliable earth for each unit and the rack.
• Each power supply in each unit has an earth leakage current of 0.65mA. The design of the electrical 
distribution system must take into consideration the total earth leakage current from all the power 
supplies in all the units. The rack will require labelling with "HIGH LEAKAGE CURRENT. Earth 
connection essential before connecting supply".
• The rack when configured with the units must meet the safety requirements of UL1950 and IEC 
60950.