5.0
I
NSTALLATION
 
AND
 C
ONFIGURATION
Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until 
instructed to do so in 8.2 - Initial Startup and Electrical Checks.
Visually inspect the UPS for shipping damage. Report any damage to the carrier and your local dealer 
or Emerson representative.
Install the Liebert
®
 GXT3
 indoors in a controlled environment, where it cannot be accidentally 
turned off. Place it where air flows unrestricted around the unit. The installation location must be 
free of water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a mini-
mum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an ambient tempera-
ture range of 0 to 40°C (32 -104°F).
5.1
Install the Main Cabinet
The Liebert GXT3 may be installed in either a tower configuration or in a rack, depending on avail-
able space and use considerations. Determine the type of installation and follow the appropriate 
5.1.1 Tower UPS Installation
To install the Liebert GXT3 as a tower:
1. Take the support bases out of the accessories bag (see Figure 9).
Figure 9
Support bases
2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the 
spacers shipped with the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 9. Each Liebert GXT3 needs two 
assembled support bases, one in the front and one in the rear.
4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3.
a. Remove the front plastic bezel cover as shown in Figure 10.
Figure 10 Remove the front plastic bezel cover
!
CAUTION
The UPS is heavy (see 12.0 - Specifications). Take proper precautions when lifting 
or moving it.
NOTE
UPS operation in sustained temperatures outside the range of 15-25°C (59°-77°F) 
reduces battery life.
Support Bases
Spacers
Connectors
Front Plastic 