Specifications
39
Table 8
UPS specifications—Liebert
®
 GXT3-6000RTL630
Model Number
GXT3-6000RTL630
Model Rating
4200W/6000VA
Dimensions, Rack Mount, W X D X H, in. (mm)
Unit
16.9 x 22.6 x 8.5 (430 x 574 x 217)
Shipping
20.9 x 29.3 x 14.8 (530 x 745 x 377)
Weight, lb (kg)
Unit
51.8 (23.5)
Shipping
66.1 (30)
Input AC Parameters
Nominal Operating Frequency
 50 or 60Hz (Factory Default, 60)
Factory Default VAC
 208VAC
User Configurable VAC
208/220/230/240VAC
(may be modified with configuration program)
Operating Voltage Range Without Battery Operation
176 – 280VAC
Maximum Allowable VAC
280VAC
Input Frequency Without Battery Operation
40 - 70Hz
Input Power Connection
L6-30P Plug (on PD-L630 power distribution box)
Output AC Parameters
Factory Default VAC
208
Output Connections
(2) L6-20R and (2) L6-30R on 12" (300mm) cords
(on PD-L630 power distribution box)
Frequency
50Hz or 60Hz, Nominal
Waveform
Sinewave
Duration Inverter Will Support Rated Load
105% to 130%
1 Minute
131% to 150%
10 seconds
151% to 200%
1 second
>200% (impact load)
At least 5 cycles
Bypass Protection Limits
Disable Bypass Operation
If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation
If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation
When the input frequency prevents synchronous operation
Environmental
Operating Temp, °F (°C)
32 to 104 (0 to 40); see Table 9
Storage Temp, °F (°C)
5 to 122 (-15 to 50)
Humidity
0% to 95% Relative Humidity, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Audible Noise
Less than 55dBA at 3.2ft. (1m) rear;
Less than 50dBA at 3.2ft. (1m) front and sides
Agency
Safety
UL 1778, c-UL Listed
EMI/EMC
FCC Class A
ESD
EN61000-4-2
Radiated Susceptibility
EN61000-4-3
Electrical Fast Transient
EN61000-4-4
Surge Immunity
EN61000-4-5
Transportation
ISTA Procedure 1A