3.1.3.1 
Mechanical Installation Cont'd 
 
(  ) 
3. 
Remove  the electrical assembly from the enclosure by 
loosening and removing the mounting hardware from the 
four corners of the base plate panel. 
 
(  ) 
4. 
The electrical assembly can now be placed in the shipping 
carton for protection. 
 
(  ) 
5. 
Proceed to mount the empty enclosure in the desired fashion.  
Recommended conduit hole locations are shown on Figure 3. 
 
(  ) 
6. 
Remove all dirt and foreign material from the enclosure, then 
re-install the electrical assembly in the enclosure after 
completing the mounting and conduit connector installation. 
 
3.1.3.2 
Electrical Wiring 
 
(  ) 
1. 
Connect the ground conductor to the ground lug located in 
the lower left hand corner of the base plate. 
 
(  ) 
2. 
Connect the remote control leads to 31955 TB1 terminals as 
indicated. 
 
L   -  120 VAC hot lead   (Input for Option -2 is  
LN - 120 VAC Neutral     to "H" terminals on Step- 
         down Transformer) 
CR  - Remote Control Common 
C1  -  Remote Control Circuit 1 
C2  -  Remote Control Circuit 2 
C3  -  Remote Control Circuit 3 for 84700-3 & -4 
C4  -  Remote Control Circuit 4 for 84700-4 
 
Note:  31955 TB1 is removable for ease of installation. 
 
(  ) 
3. 
Connect the CCR control power to 31955 TB1 terminals as 
indicated: 
 
CC1 - Control Power Feed from Regulator 
CC2 - Control Load to Tower 
 
See page 7A. 
 
(  ) 
4. 
Connect the output of the CCR to terminals R1 and R2, in 
the high voltage section, using the #12 AWG ring terminals 
provided.