2-39
2
 
LED Pattern
Where Stopped
Possible Cause
Corrective Actions
❍ EOK   (OFF)
❍ LAN  (OFF)
❍ STAT (OFF)
A
Hardware
Failure
Fatal Hardware Error.
ƒ 
Make sure the PLC has power.
ƒ 
Examine PLC Fault Table for clues.
ƒ 
Recheck PLC Programmer
configuration.
ƒ 
Power off baseplate, inspect the
Interface for loose components,
reseat the module, and Restart.
ƒ 
If the problem persists, replace the
PLC hardware.
✫ EOK  (Slowblink)
✫ LAN  (Slowblink)
✫ STAT (Slowblink)
All LEDs blink in unison.
B
Software
Loader
Software  corrupt.
Connect a PC Software Loader and load
new software. See Appendix C.
✫ EOK  (Slowblink)
❍ LAN  (OFF)
❍ STAT (OFF)
C
Waiting for
Configuration
from PLC
ƒ 
Did not configure slot using the
PLC Programmer.
ƒ 
CPU not communicating with
Ethernet Interface.
(Condition can last a maximum  of
2 seconds.)
ƒ 
Use the PLC Programmer
configuration software to configure
the Interface then store the
configuration to the PLC CPU.
ƒ 
Power cycle the PLC.
ƒ 
Clear faults and Restart Interface.
✫ EOK  (Slowblink)
/
✲/❍
  
LAN
 (ON/Traffic/OFF)
✫ STAT (Slowblink)
EOK and STAT blink in unison.
D
Waiting for IP
Address
Interface’s IP address has not been
configured or has been configured
as 0.0.0.0.
ƒ 
Use the PLC Programmer to
configure the Interface with a non-
zero IP address.
ƒ  Assign IP address over network
●EOK (ON)
/
✲/❍
 
LAN (ON/Traffic/OFF)
/
STAT(ON/OFF)
E
Operational
ƒ 
If the LAN LED is OFF,
the problem may be
network cable not
connected
ƒ 
If the STAT LED is OFF, an
exception condition has
occurred.
ƒ 
Connect cable.
ƒ 
Examine PLC Fault Table to find out
why the STAT LED is OFF.