Справочник Пользователя для Amtrol WELL-X-TROL
13
9. PUMP PROTECTION AND DIAGNOSTICS
The Well-X1
™
continually monitors pressure, cycle time and voltage to protect the well pump. The following error codes
alert the user to a potential problem, prompting service.
E1: Rapid Cycle
E2: Low Suction (low water cut-off)
E3: Voltage Protection
E5: Improper Wiring
E2: Low Suction (low water cut-off)
E3: Voltage Protection
E5: Improper Wiring
WELL-X1
™
ERROR CODES
When an error occurs, the display will flash a diagnostic code and emit an audible chirp.
ERROR CODE
POSSIBLE CAUSES AND CONTROL ACTION
E1: Rapid Cycle
Multiple cycles below a safe runtime indicate an incorrect
precharge, undersized Well-X1
precharge, undersized Well-X1
™
or waterlogged tank. Pump
continues to run.
E2: Low Suction
Pump operation below 10 psi indicates a low well level, well
piping leak, insufficient prime, failing pump or loose wiring.
Pump will shut down and attempt to restart every 60 minutes.
piping leak, insufficient prime, failing pump or loose wiring.
Pump will shut down and attempt to restart every 60 minutes.
E3: Voltage Protection
If line voltage varies outside a safe operating range, low or
high, the control will run for up to two minutes to ensure water
is available, then shut the pump off until voltage is restored to
a normal range.
high, the control will run for up to two minutes to ensure water
is available, then shut the pump off until voltage is restored to
a normal range.
E5: Improper Wiring
This error indicates the LINE and LOAD wiring is reversed at
the Well-X1
the Well-X1
™
. Correct wiring to allow proper operation.
NOTE: E4 is not used with the Well-X1
™
.