1. TABLE OF CONTENTS
GENERAL SAFETY INFORMATION ........................................................... 2
COMPONENTS ........................................................................................... 3
INSTALLATION AND SIZING CONSIDERATIONS ..................................... 4
INSTALLATION CONSIDERATIONS........................................................... 5
PLUMBING .................................................................................................. 6
WIRING ........................................................................................................ 8
STARTUP & ADJUSTMENT ........................................................................ 9
PUMP PROTECTION & DIAGNOSTICS ................................................... 13
TROUBLESHOOTING ............................................................................... 14
REPLACEMENT PARTS ........................................................................... 15 
  This  Product,  like  most  Products  under 
pressure,  may  over  time  corrode.  weaken  and  burst  or 
explode, causing serious or fatal injury, leaking or flooding 
and/or  property  damage.    To  minimize  risk,  a  licensed 
professional  must  install  and  periodically  inspect  and 
service the Product.  A drip pan connected to an adequate 
drain must be installed if leaking or flooding could cause 
property damage.  Do not locate in an area where leakage 
of the tank or connections could cause property damage 
to the area adjacent to the appliance or to lower floors of 
the structure.
 
Chlorine & Aggressive Water: The water 
quality can significantly influence the life of this Product.  
You  should  test  for  corrosive  elements,  acidity,  total 
solids and other relevant contaminants, including chlorine 
and  treat  your  water  appropriately  to  insure  satisfactory 
performance and prevent premature failure. 
NOTE:    Inspect  for  shipping  damage  and  notify  freight 
carrier  or  store  where  purchased  immediately  if  damage 
is  present.    To  avoid  risk  of  personal  injury  and  property 
damage,  if  the  product  appears  to  be  malfunctioning  or 
shows  signs  of  corrosion,  call  a  qualified  professional 
immediately.  Current copies of the Product manual can be 
viewed at www.amtrol.com.  Use proper safety equipment 
when installing.
ELECTROCUTION  AND  EXPLOSION  HAZARD!  Before 
work is performed on the Product, turn off the power to the 
Product and release all pressure in the system.
  As  in  all  plumbing  products  and  water 
storage  vessels,  bacteria  can  grow  in  this  Product, 
especially  during  times  of  non-use.    Consult  your  local 
plumbing professional regarding any steps you may wish 
to take to safely disinfect your home’s plumbing system.
 
DANGER!  EXPLOSION  HAZARD,  WHEN 
THE  WELL-X1
  HAS  BEEN  IN  SERVICE  AND  A  CHANGE 
TO  A  HIGHER  PRE-CHARGE  PRESSURE  IS  NECESSARY 
DUE TO A REQUIRED CHANGE IN THE PRESSURE SWITCH 
SETTING,  FAILURE  TO  FOLLOW  INSTRUCTION  MANUAL 
CAN  CAUSE  A  RUPTURE  OR  EXPLOSION,  POSSIBLY 
CAUSING SERIOUS OR FATAL INJURY, AND/OR PROPERTY 
DAMAGE. •  DO NOT ADJUST THE PRE-CHARGE PRESSURE 
IF THERE HAS BEEN A REDUCTION OF THE PUMP CYCLE 
TIME  OR  THE  PRE-CHARGE  PRESSURE  COMPARED  TO 
ITS  INITIAL  SETTING.    THIS  IS  BECAUSE  REDUCTION  IN 
PUMP  CYCLE  TIME  CAN  RESULT  FROM  LOSS  OF  TANK 
AIR PRESSURE WHICH IN TURN CAN MEAN THERE MAY 
BE INTERNAL CORROSION AND ANY RE-PRESSURIZATION 
OR ADDITIONAL PRESSURE COULD RESULT IN RUPTURE 
OR EXPLOSION, AND/OR PROPERTY DAMAGE.
 
RELIEF VALVE REQUIRED. A relief valve 
has been installed which is set to open at  excessive pressures 
(100 psig or more).  This will protect the Well-X1
 and other 
system components should the pressure switch malfunction 
and fail to shut the pump off.  The relief valve is installed at 
the connection of the Well-X1
 to the system piping.
  Before  attempting  any  service  and 
disassembly, shut off power to the pump.  Ensure power 
is disconnected prior to removing motor.  Ensure power is 
disconnected before cleaning is attempted.
 This control is capable of running pumps 
to  pressures  that  may  exceed  the  limitations  of  system 
components. Never set the operation pressure higher than 
that of the safe system capacity.
 This control can be adjusted to a narrow 
pressure    differential.  This  can  cause  the  pump  to  cycle 
rapidly  with  an  improperly  sized  tank,  leading  to  pump 
damage.  This  may  require  a  larger  pressure  tank  than 
normally used.
 
  CALIFORNIA  PROPOSITION  65  WARNING: 
This  product  contains  a  chemical  known  by  the  State  of 
California  to  cause  cancer  and  to  cause  birth  defects  or 
other  reproductive  harm.  (California  Installer/Contractor  - 
California law requires that this notice be given to consumer/
end user of this product.)
 For more information:  www.
amtrol.com/prop65/htm
  Every  Well-X1
  is  air  tested  to  125  psig, 
the maximum working pressure for the Well-X1
.
 The pump controller is not a disconnect. 
The  pump  may  be  activated  at  any  time.  The  electrical 
system must be considered energized at all times unless  
the circuit breaker is open. The disconnect for the controller 
must break all incoming power lines. As with a mechanical 
pressure  switch,  when  installed  with  three  wire  230  vac 
pumps  or  any  3-phase  pump,  a  standard  pump  motor 
starter or a relay must be used.
2
2. GENERAL SAFETY INFORMATION