Справочник Пользователя для AEG Protect PV.500-MH PV.500-MH
Protect PV.500_MH Operating Instructions
80000043212 BAL
39 of 68
CAN I/O monitoring systems
Fault/Message
Fault/Message
Deac-
tivat-ing
Self-
acknow-led
ging
Signalling
DOU message
Feedback signal
DC load interrupter switch Q4.1
DC load interrupter switch Q4.1
X
Q4.x: !Switch feedback fault!
Switch position Q4.1
X
Q4.x: Switch open
Feedback signal
K21 earthing PV cells
K21 earthing PV cells
X
K21: !Switch feedback fault!
Monitoring
F21 earthing circuit breaker
F21 earthing circuit breaker
X
!Miniature circuit breaker tripped!
Monitoring
F81 surge voltage arrester DC
input
F81 surge voltage arrester DC
input
X
!Overvoltage protection tripped!
Monitoring
insulation monitor level 1
insulation monitor level 1
X
!Insulation monitor warning!
Monitoring
insulation monitor level 2
insulation monitor level 2
X
!Insulation monitor alarm!
Monitoring mains voltage
auxiliary power supply mains 2
auxiliary power supply mains 2
X
!Auxiliary power supply – mains
failed!
Monitoring
F83/F84 surge voltage arrester AC
– anti-condensation heater
F83/F84 surge voltage arrester AC
– anti-condensation heater
X
F83/84: !Miniature circuit breaker
tripped!
Monitoring
F60 auxiliary power supply mains 2
F60 auxiliary power supply mains 2
X
F60: !Miniature circuit breaker
tripped!
Monitoring
F61 independent power supply
mains 1
F61 independent power supply
mains 1
X
F61: !Miniature circuit breaker
tripped!
Monitoring
Q26 AC mains disconnector
Q26 AC mains disconnector
X
Q26: Switch open
Monitoring
unit cabinet door
unit cabinet door
X
!Unit cabinet door open!
Monitoring communication CAN
I/O AC cabinet
I/O AC cabinet
X
!Communication fault with I/O
control!
Monitoring communication CAN
I/O DC cabinet
I/O DC cabinet
X
!Communication fault with I/O
control!
Monitoring
CAN I/O parameters
CAN I/O parameters
X
#I/O parameter error#