Chapter 5
5.4.10 Module Calibration
Calibration is to adjust the accuracy of ADAM module. There are
several modes for module’s calibration: Zero calibration and span
calibration. Only analog input and output modules can be calibrated.
For example: ADAM 4011, 4011D, 4012, 4016, 4017, 4018, 4018M, 5013,
5017, 5017H, and 5018.
Zero Calibration
1. Apply power to the module and let it warm up for 30 minutes.
2. Make sure the module is correctly installed and properly config-
ured for the input range you want to calibrate.
3. Use a precision voltage source to apply a calibration voltage to the
+IN and -IN terminals of the ADAM-4011, 4011D, and 4012
modules. Use a precision voltage source to apply a calibration
voltage to the Vin+ and Vin- terminals (or Iin+ and Iin-) of the
ADAM-4014D and 4016 modules. Use a precision voltage source
to apply a calibration voltage to the Vin0+ and Vin0- terminals for
ADAM-4017, 4018, and 4018M modules.
4. Click the Execute button.
Span Calibration
Click the Execute button.