Справочник Пользователя для Advantech Barcode Reader RS-485

Скачать
Страница из 348
6-58
ADAM-5000
Command Set
Note:
The ADAM-5017H module also has "Alarm Setting"
functions.  The alarm command set  for the ADAM-
5017H is the same as that for the ADAM-5013,
ADAM-5017, and ADAM-5018.  Please refer to pages
6-71 to 6-89 for this set of commands.
Command
Syntax
Command
Name
Description
Remarks
#aaSi
All Analog Data
In
Returns the input
value of all channels
for a specified
analog input
module of a
specified system in
currently configured
data format
See page
6-67
#aaSiCj
Specified
Analog Data In
Returns the input
value of a specified
channel of a
specified analog
input module of a
specified system in
currently configured
data format
See page
6-69
$aaSiER
Initialize
EEPROM Data
Initializes all
EEPROM data in a
specified analog
input module to
their default values.
Same as
ADAM-5017
See page
6-50
$aaSi0
Span
Calibration
Calibrates a
specified analog
input module to
correct for gain
errors
Same as
ADAM-5017
See page
6-51
$aaSi1
Zero Calibration Calibrates a
specified analog
input module to
correct for offset
errors
Same as
ADAM-5017
See page
6-52
5017H Analog Input