2-2
ADAM-5000
Installation Guideline
2.1
General
Environmental Specifications
The following table lists the environmental specifications that general-
ly apply to the ADAM-5000 system (System kernel and
I/O modules).
Specification
Rating
Storage temperature
-13 to 185°F (-25 to 85°C)
Ambient operating
temperature
14 to 158°F (-10 to 70°C)
Ambient humidity*
5 to 95%, non-condensing
Atmosphere
No corrosive gases
Equipment will operate below 30% humidity.  However, static
electricity problems occur much more frequently at lower humidity
levels.  Make sure you take adequate precautions before you touch
the equipment.  Consider using ground straps, antistatic floor   cover-
ings, etc. if you use the equipment in low humidity environments.
Power Requirements
Although the ADAM-5000 systems are designed for standard
industrial unregulated 24 V
DC
 power supply, they accept any power
unit that supplies within the range of +10 to +30V
DC
. The power supply
ripple must be limited to 100 mV peak-to-peak, and the immediate ripple
voltage should be maintained  between +10 and +30 V
DC
.
Diagnostic Indicators
Diagnostic indicators are located on the front panel of the ADAM
system. They show both normal operation and system status in your
remote I/O  system.  The indicators are:
System status (PWR, RUN)
Communication status (TX, RX)
I/O module status