Справочник Пользователя для Advantech Barcode Reader RS-485

Скачать
Страница из 348
4-22
ADAM-5000
I/O Modules
Calibration voltage (ADAM-5017H)
Table 4-9: Calibration voltage of ADAM-5017H
(1)  Note:
You can substitute 2.5 V for 20 mA if you remove the
current conversion resistor for that channel.  Howev-
er, the calibration accuracy will be limited to 0.1%
due to the resistor's tolerance.
Module
Input Range
Code (Hex)
Input Range
Span Calibration
Voltage
5017H
00h
±10 V
+10 V
01h
0 ~ 10 V
+10 V
02h
±5 V
+5 V
03h
0 ~ 5 V
+5 V
04h
±2.5 V
+2.5 V
05h
0 ~ 2.5 V
+2.5 V
06h
±1 V
+1 V
07h
0 ~ 1 V
+1 V
08h
±500 mV
+500 mV
09h
0 ~ 500 mV
+500 mV
0ah
4 ~ 20 mA
*(1)
0bh
0 ~ 20 mA
*(1)