 Geo Brick Drive User Manual 
Drive Structure and Troubleshooting 
 280 
Reloading Boot and Communication Firmware 
The boot and firmware .IIC files are required for this procedure. They are normally obtained directly from 
Delta  Tau,  or  downloaded  from  the  PMAC  forum  Webpage.    The  following  steps  ensure  proper 
configuration:  
 
 
Caution 
Downloading  the  wrong  boot  or  communication  files  will  severely 
corrupt the functionality of the communication processor.   
 
 
Step1:  Hold the BOOT SW switch down 
 
Step2:  Click on Store Boot 
 
Step3:
  The utility will prompt for the boot file. MAKE SURE you open the correct .IIC file (ending with 
BootFx2.iic) and wait for “firmware load successful” message 
 
 
 
Step4:  Click on Store F/W 
 
 
Note 
The BOOT SW switch button can be released temporarily (between 
file downloads). But it MUST to be held down the entire time the boot 
or firmware files are being written. 
 
Step5:
  The utility will prompt for the Firmware file. MAKE SURE you open the correct .IIC file (ending 
with ETHUSB307FX2.iic) and wait for “firmware load successful” message 
 
 
 
 
 
 
Step6:  Release the BOOT SW switch. Click Done, and recycle logic power (24V) on the Brick.