Turbo Clipper Drive User Manual 
 
Motor Setup Guidelines 
71 
Manual Phasing Method:
 Useful for troubleshooting and testing for “good” phase finding 
output value used in 2-guess or stepper method. It can be used regardless of the type of feedback.  
The manual phasing method consists of locking the motor tightly to one of its phases and 
resetting the Phase position register in PMAC. It is useful for troubleshooting, rough phasing and 
testing for a “good” phase finding output value.  
Steps to follow, or implement in a PLC: 
 
a.  Record the values of Ixx29, and Ixx79 to restore them at the end of test. 
b.  Set Ixx29=0, and write a positive value to Ixx79 then issue a #nO0. 
 
500 is a reasonable conservative starting value for Ixx79. Adjust appropriately 
 
(most likely increase) to force the motor (unloaded) to lock tightly onto a phase. 
c.  Set Phase Position register to zero, Suggested M-Variable Mxx71=0 
d.  Issue a #nK to kill the motor 
e.  Restore Ixx29, and Ixx79 to their original values 
f.  Clear Phasing search error bit, Suggested M-Variable Mxx48=0 
g.  The motor is now ready to jog/close the loop 
 
Motor 1 Manual Phasing Example PLC: 
#define Mtr1PhasePos   
M171 
; Motor 1 Phase Position Register, Suggested M-Variable 
Mtr1PhasePos->X:$B4,0,24,S 
#define Mtr1PhaseErrBit 
M148 
; Mtr1 Phasing Search Error Bit, Suggested M-Variable 
Mtr1PhaseErrBit->Y:$C0,8 
 
 
Open plc 3 clear 
I5112=500*8388608/I10 while(I5112>0) Endw 
P129=I129 P179=I179 
; Store Ixx29, and Ixx79  
I129=0 I179=1000 
; Set Ixx29=0 and Ixx79 to positive value (adjustable) 
I5112=100*8388608/I10 while(I5112>0) Endw 
; 100 msec delay 
CMD"#1o0" 
 
; Issue 0% open loop command output 
I5112=3000*8388608/I10 while(I5112>0) Endw 
; 3 seconds delay to allow motor to settle 
Mtr1PhasePos=0  
; Set phase register to zero 
I5112=500*8388608/I10 while(I5112>0) Endw 
; 1/2 second delay 
CMD"#1K" 
 
; Kill Motor 
I5112=100*8388608/I10 while (I5112>0) Endw 
; 100 msec delay 
I129=P129 I179=P179 
; Restore Ixx29 and Ixx79 to original values 
Mtr1PhaseErrBit=0 
; Clear Phasing search error bit 
I5112=500*8388608/I10 while (I5112>0) Endw 
; 1/2 second delay 
Dis plc 3 
 
; Disable PLC, run only once 
close 
 
2-Guess Phasing Method:
 Rough phasing method for motors with relatively small loads or 
quick setups for testing. Typical (example) values: 
Ixx73=1200  ; Phase Finding Output Value (Adjustable). Units of 16-bit DAC 
Ixx74=8 
; Units of Servo Cycles 
Ixx80=4 
; 2-guess method, no absolute position read, no power-on phasing 
  
Stepper Phasing Method:
 Finer than the 2-guess method, usually used on motors with 
significant loads. Typical (example) values: 
Ixx73=1200  ; Phase Finding Output Value (Adjustable). Units of 16-bit DAC 
Ixx74=80 
; Units of Servo Cycles * 256 
Ixx80=6 
; Stepped method, no absolute position read, no power-on phasing