Figure 4.  RS-422 Wiring Diagram 
 
RS-485 and RS-422 Termination 
 
A jumper labeled “TERM” provides termination for the RS-
485/422 receiver. The termination resistor is a 120-ohm resistor 
placed between the RD (A) and RD (B) lines. To use this 
termination, place the jumper in the "IN" position.  Refer to Figure 2 
for the location of this jumper.  If there is no need for termination, 
place the jumper in the "OUT" position. For more discussion of 
termination refer to B&B Electronics’ free RS-422/485 Application 
Note. 
Power Supply 
 
The 485DSS requires an unregulated DC power source that will 
supply +12 volts at 100 milliamps.  Connect the positive side of the 
power source to the +12VDC terminal block and the common side of 
the power source to the GND terminal block.  Refer to Figure 2 for 
the location of the terminal blocks and the polarity. B&B Electronics' 
power supply Model 485PS2 is available for the 485DSS.