Справочник Пользователя для Bosch Appliances Home Security System D9412GV2

Скачать
Страница из 74
D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0   Off-Board Points 
 
44 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
 
Figure 16:  Connecting D8128D OctoPOPITs to the D9412GV2 
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 3.5
Signaling
Line
Circuits
32
31
30
29
28
27
ZONEX OUT 2
26
25
ZONEX IN 2
ZONEX POWER +
24
ZONEX COMMON
23
21
22
1
5
2
3
2
4
6
6
7
8
9
8
6
6
11
10
12
GRN
D5200/D5360
PROG CONN
Point 8
S3 Option
Closed = 1K
Ω
 EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 K
Ω
 
1 -  Zonex Bus 1, Switch 1 ON (Points 9 to 72) 
2 -  Bus 1 
3 -  First address on Zonex Bus 1 
4 -  Last address on Zonex Bus 1 
5 -  Zonex Bus 1, Switch 1 OFF (Points 73 to 127) 
6 -  Sensor loops 
7 -  Zonex Bus 2, Switch 1 ON (Points 129 to 192) 
8 -  Bus 2 
9 -  First address on Zonex Bus 2 
10 -  Last address on Zonex Bus 2 
11 -  Zonex Bus 2, Switch 1 OFF (Points 193 to 
240) 
12 -  On-board points 
 
 
 
Refer to Address Switches in Section 9.4.4 Setting the OctoPOPIT Switches on page 41 for 
information about making these switch settings.