Справочник Пользователя для Beckett BRYAN STEAM CF1400

Скачать
Страница из 24
17
Form 6104 BCF23-R05
Table 4a. CF1400 Initial indicator 
adjustment plate settings
Figure 12 – Adjusting plate initial setting, typical
Table 4b. CF2300 Initial indicator 
adjustment plate settings
CF1400
Tube
Head Position
Damper Position
Approximate
Head Setting
Firing Rate
(gph)
Approximate 
Air Damper 
Setting
Firing Rate 
(gph)
A
0
4.00
0
--
1
4.50
10
--
2
5.00
20
4.00
3
6.00
30
5.00
4
7.00
40
7.00
5
7.50
50
8.00
6
8.00
60
10.00
7 9.00
70
11.00
8
9.50
80
--
9
10.00
90
--
10
11.00
100
--
--
--
110
--
--
--
120
--
B
0
7.00
0
--
1
7.50
10
--
2
8.00
20
--
3
9.00
30
--
4
10.00
40
7.00
5
10.50
50
8.00
6
11.00
60
10.00
7 12.00
70
11.00
8
13.00
80
12.00
9
13.25
90
12.50
10
13.60
100
13.00
--
--
110
13.25
--
--
120
13.60
CF2300
Tube
Head Position
Damper Position
Approximate 
Head Setting
Firing Rate 
(gph)
Approximate 
Air Damper 
Setting
Firing Rate 
(gph)
A
0
11.0
0
--
1
12.0
10
7.0
2
13.0
20
10.0
3
14.0
30
13.0
4
15.0
40
14.0
5
16.0
50
15.0
6
17.0
60
16.0
7
18.0
70
17.0
8
19.0
80
18.0
9
20.0
90
19.0
--
--
100
20.0
B
0
12.5
0
--
1
13.0
10
10.0
2
14.0
20
13.0
3
15.0
30
14.0
4
16.0
40
15.0
5
17.0
50
16.0
6
18.0
60
17.0
7
18.5
70
18.0
8
19.0
80
18.5
9
20.0
90
19.0
--
--
100
20.0
Legend
b Spline nut for securing nozzle line
c Bottom acorn nut (for head adjustments)
d Top acorn nut (for setting dim. Z only - do not 
loosen after setting Z)
e Indicator adjusting plate
f Secondary adjusting plate
g Primary adjusting plate
h Copper oil line from oil valve to nozzle line