XIV.  Troubleshooting
A.  Troubleshooting problems where no error code is displayed:
TABLE 14.1:  NO ERROR CODE DISPLAYED
CONDITION
POSSIBLE CAUSES
Display Blank, Fan off, LWCO lights off
• No 120VAC Power at boiler. Check breaker and wiring between breaker panel 
and boiler  
Display Panel Blank, Fan running 
• Loose 120VAC connection wiring between boiler J-Box and MCBA 
• Blown “F1” fuse in MCBA (see Figure 13.2 for location). Replace with 5A fuse 
provided
Display reads “U.125” continuously, Fan running
• Defective AT250 transformer
• Blown “F3” fuse in MCBA (see Figure 13.2 for location). Replace with 4A slow-
blow fuse provided
Boiler not responding to call for heat, Status code on 
display =”0” (see Figure 11.1) 
• Boiler is not seeing call for heat. Check thermostat or zone wiring for loose 
connection, miswiring, or defective thermostat/zone control.
Boiler fi res, but display panel is blank
• Loose ribbon cable 
• Defective display
WARNING
Turn off power to boiler before replacing fuses or working on wiring.