D9412GV2/D7412GV2 | Program Entry Guide | 4.0  RADXPNTS 
EN | 101 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
The Cross Point feature does not activate when a 
fault occurs on Controlled points (Point Types 1, 2 
and 3) in the disarmed, entry delay, or exit delay 
states. Refer to Section 
P## Alarm Verify 
Default: 
Refer to the program record sheet 
on page 
Selection:  Yes or No 
142 for additional programming requirements 
to program the Cross Point Timer. 
Enable alarm verification on this 
point. 
Yes 
 
If an abort window delay is needed for the cross zone 
alarms, all cross zone points in the group must have 
Alarm verification points must be 
programmed as resettable. 
 (refer to page 102)set to Yes
 
 
The Cross Point function applies only to 
Disable alarm verification on this 
point. 
No 
Instant Alarm conditions. It does not 
apply to Trouble or Supervisory 
Use this option only with Fire points to designate them 
for alarm verification. 
conditions. 
For SIA CP-01 Compliance: 
When an Alarm Verification point enters into alarm, 
the control panel removes power to all Resettable 
points for the duration programmed in A# Verify Time 
in Section 
P## Cross Point can be set to Yes or No
 
2.9 Area Parameters on page 36. If the 
point (or another Resettable point in the area) is still 
faulted, or returns to a faulted state within 60 sec after 
the initial verification time reset, an alarm is 
generated. 
P## Fire Point 
Default: 
No 
Selection:  Yes or No 
Yes 
This point is a Fire point. 
No 
This point is not a Fire point. 
 
 
To meet UL 864 requirements, set this 
parameter to Yes for all applicable Fire 
points. 
 
Use this option to make a 24-hour point a Fire point. 
This option makes this point the highest priority event 
in the control panel when an alarm occurs for both 
reporting and displaying on the keypad. Refer to 
Section 4.2.2 Characteristics of a Fire Point on page 
92. 
 
 
You should dedicate a fire annunciation 
device to all your Fire points if they are 
assigned to a single area in a multiple 
area system. Special red keypads and 
annunciators with specific keys for fire 
systems are designed for this type of 
application (D1256RB and D1257RB). 
 
 
 
Do not use the Cross point function for 
Fire points. 
 
During a Fire Walk Test the reset time is 
5 sec. The time programmed in A# Verify 
Time
 is ignored.  
 
P## Resettable 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
This point is reset by the Reset 
Sensor? function and during the 
alarm verification sequence. 
Yes 
No 
This point is not resettable. 
 
To meet UL 864 requirements, set this 
parameter to Yes for applicable 
resettable points. 
 
Use this option if this is a Powered point that requires 
interruption of power to reset a latched alarm 
condition. The Resettable point option is typically 
used with smoke detectors and glass break detectors. 
When initiated (either through a Fire Walk Test or the 
keypad’s Reset Sensor? function) or when the remote 
programming software (RPS) interrupts power to the 
device for 5 sec, a Sensor Reset report is sent to the 
central station receiver.