As shown in Fig. 2-1, output voltage never decreases below 90% of full output rating 
during the source transfer.  Output voltage recovers to full rated output within 2 cycles 
following transfer.  Under the test conditions in which the waveform was recorded, 
output voltage was measured to be 86.30 volts RMS with 80% of full rated load applied. 
 
Video-only services using equipment powered by standby power supplies should 
exhibit little if any disturbance within the customers’ homes during a source transfer.  
On the other hand, critical services such as VoIP, telephony grade communications 
and data transfer may experience undesired disturbances from source transfers 
between commercial AC line and inverter power.  Such services may be highly 
intolerant of any power anomolies, even minor disturbances that would never be 
noticed on video-only services.  For mission-critical services requiring an exceptionally 
high degree of power integrity, system operators are advised to consider using one of 
the MP Plus Series true-UPS power supplies offered by Multilink Broadband.  Contact 
you local Multilink sales representative for further information. 
 
The power supplies documented in this instruction manual have been designed to 
support optional HMS status monitoring.  The HMS protocol supports communication 
between the power supply and the monitoring device via an RS-485 serial port in an 
external modem.  HMS status monitoring may be installed either at the factory or in the 
field as an added option.   
 
Blackhawk Series Product Features: 
 
o
 60/75/90 VAC output operation; easily user selectable. 
o
  Serial status monitoring available, compatible with HMS-022 protocol. 
o
  High efficiency for economical line operation and longer standby run time.               
o
 Ferroresonant 
output: 
filters and regulates load power. 
o
  Status at a glance display. 
o
  High input power factor, typically 0.9 or better (line mode). 
o
  Temperature compensated charger with battery temperature sensor. 
o
  Robust inverter circuits with compact forced-air cooling. 
o
  PM (pole-mount) and GM (ground-mount) enclosure options. 
  
 
Unpacking and Inspection 
 
Before installing this equipment, inspect the power supply for shipping damage or missing 
components.  If the power supply or other items were damaged in shipment, file a damage 
claim with the shipping company and contact your Multilink Broadband representative 
immediately.  Be sure to retain the original shipping carton and all packing material for the 
power supply until you are certain that warranty return will not be required. 
 
All Blackhawk Series power supplies include: 
     Power supply, ready for installation in cabinet 
Battery temperature sensor cable 
Installation and operating instructions 
 
10