WARNING
!
Do  not  use  on  circuits  exceeding  specified  voltage. 
Higher voltage will damage control and could cause 
shock or fire hazard.
Do  not  short  out  terminals  on  gas  valve  or  primary 
control to test. Short or incorrect wiring will damage 
thermostat  and  could  cause  personal  injury  and/or 
property damage.
Thermostat  installation  and  all  components  of  the 
system shall conform to Class II circuits per the NEC 
code.
1F83-261
Non-Programmable Electronic Digital
Multi-Stage Thermostat
INSTALLATION AND OPERATION INSTRUCTIONS
FAILURE TO  READ  AND  FOLLOW  ALL  INSTRUCTIONS  CAREFULLY 
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE 
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
 
 DESCRIPTION
•  Backlit display when any key is pushed
•  °F/°C convertibility
•  Temperature range 45° to 90°F
•  R, C, W, W2, G , Y and Y2 terminals
•  Optional C terminal (Dual Power option)
•  Setpoint storage in case of power loss
•  2 “AA” Energizer
®
alkaline batteries included
Operator:  Save these instructions for future use!
Your new White-Rodgers Digital Thermostat uses the technology
of a solid-state microcomputer to provide precise time/temperature
control. This thermostat offers you the flexibility to design heating
and cooling programs that fit your needs.
Features:
•  Simultaneous heat and cool setpoint storage
•  Pre-set temperature control
•  LCD continuously displays setpoint and room temperature
 
 PRECAUTIONS
This thermostat is intended for use with a low voltage system;
do not use this thermostat with a line voltage system. If in doubt
about whether your wiring is millivolt, line, or low voltage, have it
inspected by a qualified heating and air conditioning contractor
or electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
CAUTION
!
To prevent electrical shock and/or equipment damage, 
disconnect electric power to system at main fuse or 
circuit breaker box until installation is complete.
 
 SPECIFICATIONS
ELECTRICAL DATA
Electrical Rating:
 
20 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.5 Amps (Load per terminal)
 
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range: 
0 to 90% RH (non-condensing)
Shipping Temperature Range: 
-4°F to 150°F
APPLICATIONS
For use with:
•  Heat/cool systems with up to two stages heat,
 two stages cool
DO NOT USE WITH:
•  Millivolt systems
•  Systems exceeding 30 VAC and 1.5 amps
•  3-wire zoned hydronic heating systems
PART NO. 37-6321B
Replaces 37-6321A
1014
www.white-rodgers.com
www.emersonclimate.com