INSTALLER/CONFIGURATION MENU
Press the Menu button for at least 5 seconds. The display will show item #1 in the table below. Press Menu to advance to the
next menu item. Press 
 or 
 to change a menu item.
MENU
PRESS
DISPLAYED
Press 
 or 
 to
REF.
HP
SS BUTTON (FACTORY DEFAULT)
select from listed options
COMMENTS
1
1
MENU
On (Cool O)
Heat b On
Reversing Valve Output (Heat Pump switch S8
must be in the Heat Pump HP position)
2
2
1
MENU
P (2)
P 3, P 0
Selectable Programs Per Week
(For programmable thermostat only)
3
3
2
MENU Cool Saving CS (OFF)
Cool Saving CS On
Select Cool Savings on or off
CS (3)
6, 5, 4, 2, 1
Selects Cool Savings value 1 (low) to 6 (high)
4
4
3
MENU
E (On)
E OFF
Selects Energy Management Recovery (EMR)
on or off
5
4
MENU
CR Heat
FA, SL
Adjustable Anticipation (Heat) (only when
(ME)
heat pump switch is at the SS position)
6
5
MENU
CR Cool
SL
Adjustable Anticipation (Cool) (only when
(FA)
heat pump switch is at the SS position)
7
5
MENU
CR Heat Pump
SL
Adjustable Anticipation (Heat Pump) (only
(FA)
when heat pump switch is at the HP position)
8
6
6
MENU
CL (OFF)
CL On
Compressor Lockout Time
9
7
7
MENU
Auto Heat
Heat Cool Off,
System Mode Configuration
Cool Off
Heat Off with Fan icon,
with Automatic Changeover
Heat Off without Fan
icon, Cool Off,
Auto Off
Cool Off Heat
Heat Off with Fan icon,
System Mode Configuration
Heat Off without
without Automatic Changeover
Fan icon, Cool Off
10
8
8
MENU
L (On)
L OFF
Selects Display Light on or off
11
9
9
MENU
0 HI
1 HI, 2 HI, 3HI, 4 HI,
Adjustable Ambient Temperature Display
1 LO, 2 LO, 3 LO, 4 LO
12
10
10
MENU
F
C
Selects Fahrenheit/Celcius Temperature Display
13
11
11
MENU
Change Filter (OFF)
Change Filter On
Selects Filter Change-out Indicator
Change Filter 200 h
25 h to 1975 h in
When on, selects time in 25 hour increments
25-hour increment
14
12
12
RUN
Returns to Normal Operation
INSTALLER/CONFIGURATION MENU
1)
Select Reversing Valve Output (Heat Pump switch S8
must be set at HP) – The O/B option is factory set at
"O" position. This will accommodate the majority of  heat
pump applications, which require the changeover relay to
be energized in COOL. If  the thermostat you are replac-
ing or the heat pump being installed with this thermostat
requires a "B" terminal, to energize the changeover relay
in HEAT, the O/B option should be set at "B" position.
2)
Program Options: This control can be configured for 5/2
day or 5/1/1 day programming or non-programming mode.
The default setting is P2, indicating 5/2 day programming.
The programs per week can be toggled to P3 or P0 by
pressing the 
 or 
 keys. A selection of  0 Days for
non-programmable will eliminate the need for EMR, and
that step in the menu will be skipped.
3)
Select Cool Savings™: With Cool Savings™ enabled,
the thermostat will make small adjustments to the setpoint
temperature during periods of  high demand to reduce AC
system running time and save energy. When the cooling
system has been running for more than 20 minutes,
humidity in the home will be lower and a higher setpoint
temperature will feel comfortable. After 20 minutes of  run
time, the thermostat will start increasing the setpoint
temperature in steps of  less than one degree as the
system continues to run. These adjustments will eventu-
ally cause the system to satisfy the thermostat to turn the
system off  and reduce the energy consumption. When
the Cool Savings™ feature is active and making adjust-
ments, the display will show “
Save” next to the setpoint
temperature. The amount of  the adjustments to the
setpoint temperature is dependent on the Cool Savings™
value that is set, 1 being the least adjustment and 6 being
the most adjustment. With this feature set to OFF, no
change will occur when the AC system is continuously
running during the periods of  high demand. Periods of
high demand will normally occur during the late afternoon
and early evening on the hottest days of  the summer.