Каталог для White Rodgers 752-2 Automatic Change-Over Control

Скачать
Страница из 1
AUTOMATIC CHANGE-OVER SWITCH
SPDT Control Provides Automatic Change-Over of Thermostat to 
Operate Zone Valve on Combination Hot and Chilled Water Systems
FEATURES
• Epoxy resin seal protects bimetallic disc and Snap-Action contacts from dust, dirt
  and corrosion.
• Furnished with removable spring clip to attach control to tubing.
• SPDT switch connects heating side of thermostat to two-wire zone valve when hot
  water is circulated through tubing.
• SPDT switch connects cooling side of thermostat to two-wire zone valve when
  chilled water is circulated through tubing.
• Curved sensing element provides maximum contact with tubing.
  Model Number 
Model Number 
 
Motor Rating 
Pilot Duty 
Resistive
  without conduit  
with conduit   
Switch 
Full Load 
Lock Rotor 
120 / 240 /   (non-inductive)
 
 connector 
connector 
Action 
120 VAC 
240 VAC 
120 VAC 
240 VAC 
277 VAC  120 / 240 / 277 VAC
 
752-1 
752-2 
SPDT 
7.5A 
3.75A 
45.0A 
22.5A 
125 VA 
15A
752-1
SPECIFICATIONS
Electrical Connections . . . . . . . . . . . . . . .  
12” red, brown and black leads,
   
  105°C insulated, No. 18 wire
Temperature Settings . . . . . . . . . . . . . . . .   Red-Black: open on rise @ 85°F,
   
  close @ 70°F
   
  Red-Brown: close on rise @ 85°F,
   
  open @ 70°F
Ambient Temperature . . . . . . . . . . . . . . . .   221°F maximum
TYPES FOR USE WITH ½” TUBING 
(
5
/
8
 O.D.)
CONTRACTOR TIP
: USE WITH
ZONE VALVES ON PAGES 103-104 
FOR HEAT / COOL APPLICATIONS.
REMOTE TEMPERATURE
CONTROLS
TYPES FOR USE WITH 1/2" TUBING (5/8" O.D.)
TYPES
SWITCH 
ACTION
A.C MOTOR RATING
PILOT
DUTY
(120V or 
240V)
NON-IN-
DUCTIVE 
(120 or 
240V)
WITHOUT
CONDUIT
CONNECTOR
WITH
CONDUIT
CONNECTOR
FULL LOAD
LOCKED ROTOR
120V
240V
120V
240V
752-1
752-2
SPDT
7.5A
3.75A
45.0A
22.5A
125 VA
15.0A
TYPES FOR USE WITH 3/4" TUBING (7/8" O.D.)
752-1
SPDT
7.5A
3.75A
45.0A
22.5A
125 VA
15.0A
5
4
3
2
1
5
4
6
6
5
4
6
5
4
6
3
2
1
3
2
1
3
2
1
4
2
2
1
3
4
2
2
1
3
4
2
2
1
3
4
2
2
1
3
BLACK
RED
BROWN
W/R
CHANGE-
TRANSFORMER
TYPE 1361 TWO-WAY-
ZONE VALVES.
WHEN USING ONE TRANSFORMER PER VALVE.
OMIT THIS LINE BETWEEN ALL VALVES.
OVER
SWITCHES
25V.
120V.
SPECIFICATIONS
 
Electrical Connections 
 12” red, brown, and black leads, 105ºC insulated, No. 18 wire.
 
Temperature Settings 
  Red-Black, open at 85ºF + 6º
 
                      Red-Brown, open 70ºF + 6º   
 
Ambient Temp. 
– 220
ºF Max.
Typical diagram using Type 1361 valves (25 volts)with Changeover Switch. Boiler, chiller, 
and circulator operation are independent of thermostat demand.
www.white-rodgers.com
105
105
HYDRONIC /  APPLIANCE