Каталог для White Rodgers 24A34-1 Electric Heat Sequencer

Скачать
Страница из 1
 
Model 
 
 
Timings – ON 
Timings – OFF
  Number 
Timings  Switches M1-M2  M3-M4  M5-M6  M7-M8  M9-M10  M1-M2  M3-M4  M5-M6  M7-M8  M9-M10
 
24A34-1 
1-20 
– 
– 
– 
– 
40-110 
– 
– 
– 
 
24A34-2 
– 
– 
30-90 
– 
– 
– 
– 
1-30 
– 
 
24A34-3 ➀ 
1-20  1-20 
– 
– 
– 
40-110
 
40-110
 
– 
– 
 
24A34-4 
– 
– 
30-90  30-90 
– 
– 
– 
1-30  1-30 
 
24A34-5 ➀ 
1-110  1-110  1-110 
– 
– 
1-110  1-110  1-110 
– 
 
24A34-6 ➀ 
1-110  1-110  1-110  1-110 
– 
1-110  1-110  1-110  1-110 
 
24A34-14➀➁
 
1-160  1-160  1-160  1-160  1-160  1-160  1-160  1-160  1-160  1-160
 
24A34-21 
1-20 
– 
– 
– 
– 
1-50 
– 
– 
– 
 
24A34-22 
15-45 
– 
– 
– 
– 
1-30 
– 
– 
– 
 
24A34-23 
25-55 
– 
– 
– 
– 
15-45 
– 
– 
– 
 
24A34-24 
30-75 
– 
– 
– 
– 
1-40 
– 
– 
– 
 
24A34-25 
40-90 
– 
– 
– 
– 
1-30 
– 
– 
– 
 
24A34-26 
1-20  30-90 
– 
– 
– 
40-90  1-30 
– 
– 
 
24A34-27 
1-160  1-160 
– 
– 
– 
1-160  1-160 
– 
– 
 
24A34-28 ➂ 
1-160  1-160 
– 
– 
– 
1-160  1-160 
– 
– 
 
24A34-29 
15-35 
– 
– 
– 
– 
25-55 
– 
– 
– 
 
24A34-36 
1-20  30-45 
– 
– 
– 
45-110  1-30 
– 
– 
 
24A34-37 
1-110 
– 
– 
– 
– 
1-110 
– 
– 
– 
MODEL 24A34 ELECTRIC HEAT SEQUENCERS
Direct Replacement for Most Fan / Heat Sequencing Functions.
Terminal Markings are Equivalent to Competitive Types
FEATURES
• Replaces Honeywell, MARS, TOD,
  GEMLINE, Klixon (Texas Instruments).
• 24V input control.
• Multi-poise mounting.
 
 
Resistive (Non-Inductive) 
Motor Ratings (Inductive)
 
VAC 
Watts 
Amps 
Full Load 
Locked Rotor 
Pilot Duty
 
120 
3000 
25.0 
14.0A 
72.0A 
125 VA
 
240 
6000 
25.0 
7.0A 
42.0A 
125 VA
 
480 
6000 
12.5 
– 
– 
480 VA
ELECTRICAL RATINGS – SINGLE LOAD CONTACT RATINGS (ALL MODELS)
• Any contacts (except M1 & M2) can be
  used as auxiliary contacts.
• Double quick-connect terminals for
  combination loads.
SPECIFICATIONS
Ambient Temperature Rating . . . . . . . . . .   -50 to +165°F
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . .   U.L. component recognized
TABLE NOTES:
 M1-M2 and M3-M4 are always first switches
  to turn ON and last to turn OFF. All other
  switches are random ON and random OFF
  24A34-14 Switch contacts designated 
  F
-  F
2
 instead of M
- M
2
  24A34-28 is 2 pole double throw
  These contacts switch simultaneously
NOTE: Underwriters Laboratories requires a
fan interlock circuit to insure the blower
remains operating whenever more than one 
sequencer is used. The fan interlock should
be the M
1
 / M
2
 contacts of the second or third 
sequencer.
All M
1
 / M
2
 contacts are wired to the blower mo-
tor so that any sequencer that is energized will
keep the blower ON.
COMBINED LOAD RATING TABLE
(ALL MODELS)
30A @ 240 VAC – TOTAL,
23A Non-Inductive + 7 FLA / 42 LRA Inductive,
ON Time:  Elapsed time to make contacts after
 
heater is energized (min. to max.)
OFF Time:  Elapsed time to break contacts after
 
heater is de-energized (min. to max.)




24A34-3
  Model 
 
 
Timings
  Number 
Timings 
Switches 
ON 1-3 
OFF 1-3
 
24A34-15 
1-60 
75-95
24A34-15 HEAT PUMP CONTROL
FEATURES
• Used in heat pump air handler applications.
• Provides a delay off to the blower motor in cooling mode.
• Single pole double throw.
 
 
Resistive (Non-Inductive) 
Motor Ratings (Inductive)
 
VAC 
Watts 
Amps 
Full Load 
Locked Rotor 
Pilot Duty
 
120 
3000 
25.0 
14.0A 
72.0A 
125 VA
 
240 
6000 
25.0 
7.0A 
42.0A 
125 VA
ELECTRICAL RATINGS – NORMALLY OPEN CONTACTS 1-3
 
 
Resistive (Non-Inductive)
 
VAC 
Watts 
Amps 
Pilot Duty
 
120 
1200 
10.0 
125 VA
 
240 
1200 
5.0 
125 VA
ELECTRICAL RATINGS – NORMALLY CLOSED CONTACTS 1-2
ELECTRIC HEAT
PRODUCTS
Indicates Canadian Model Number: call 1-800-305-6953 to order
HEA
TING
www.white-rodgers.com
71