1
Part Number 550-110-032/0607
Standing Pilot Boilers — Control Supplement
Figure 9 
Manually opening vent damper
In event of vent damper failure:
Effikal vent damper
If troubleshooting chart recommends replacing actuator and actuator is
not immediately available, damper blade can be fixed in an open position
to allow boiler operation.
Manually turning blade can cause actuator 
damage
.  Follow  these  instructions  only  in  case  of  no  heat  or  damper
actuator malfunction.
1.  Move damper service switch to
Hold Damper Open
position. Apply call
for heat to boiler. Damper blade should then rotate to open position
and boiler will fire.
.  If step 1 does not open damper, manually rotate damper blade to open
position using wrench or pliers on flat shaft between damper and actua-
tor. Boiler will fire. Verify that damper service switch is in Hold Damper
Open position (Figure ).
.
Do not leave vent damper permanently in this position.
Replace actua-
tor immediately. If vent damper is left in open position, boiler will not
operate at published efficiencies.
Johnson Controls vent damper
If troubleshooting chart recommends replacing actuator and actuator is
not immediately available, damper blade can be fixed in an open position
to allow boiler operation. Follow these instructions only in case of no heat
or damper actuator malfunction. See Figure .
1.  Turn off power to boiler.
 Failure to turn off power to boiler can result in severe personal
injury, death or substantial property damage.
.  Refer to vent damper manufacturer’s instructions for procedure to fix
vent damper in open position.
.  Turn on power to boiler.
.  Using wrench or pliers on flat shaft section, manually rotate damper
blade until green light turns on. Boiler will fire (Figure ).
.  Do not leave vent damper permanently in this position. Replace actua-
tor immediately. If vent damper is left in open position, boiler will not
operate at published efficiencies.
Before troubleshooting
1.  Have a voltmeter that can check 10 VAC,  VAC,
and a continuity tester.
.  Check for 10 VAC (minimum 10 to maximum
1) to boiler.
.  Be sure pilot is lit. See “Lighting instructions” on
pages 1-18 for details.
.  Make sure thermostat is calling for heat and contacts
(including  appropriate  zone  controls)  are  closed.
Check for VAC between thermostat wire nuts and
ground.
 Burner  access  panel  must  be  in  posi-
tion  during  boiler  operation  to  prevent
momentary flame rollout on ignition of
main  flame.  Severe  personal  injury  or
substantial property damage will result.
 Never  jumper  (bypass)  any  device  ex-
cept  for  momentary  testing  as  outlined
in  Troubleshooting  Charts.  Substantial
property damage and/or severe personal
injury could occur.
 Label  all  wires  prior  to  disconnection
when  servicing  controls.  Wiring  errors
can cause improper and dangerous opera-
tion.
 Verify proper operation after servicing. See
vent damper manufacturer’s instructions
packed with vent damper for additional
information.  Failure  to  comply  could
result in severe personal injury, death or
substantial property damage.
Troubleshooting