Листовка для Z-Com SRZ IMS01T05-E2

Скачать
Страница из 2
(Continued on the next page  )
 
 
Module Type Controller SRZ 
 
 
IMS01T05-E2 
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure 
proper operation of your new instrument, carefully read all the instructions in this manual. Please 
place this manual in a convenient location for easy reference. 
 
This manual describes the mounting, wiring and specifications only. For the basic operations, see 
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-E ), Z-COM PLC 
Communication Data List (IMS01T15-E ) and Z-COM Host Communication Quick Instruction 
Manual (IMS01T09-E ). For the detail handling procedures and various function settings, please 
refer to separate Z-COM Instruction Manual (IMS01T07-E ).
 
 
The above manuals can be downloaded from our website: 
URL: http://www.rkcinst.com/english/manual_load.htm
 
 
 
Accessories check 
 
 
 
 
 
 
 
Safety precautions 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
This is a Class A instrument. In a domestic environment, this instrument may cause radio 
interference, in which case the user may be required to take adequate measures. 
 
This instrument is protected from electric shock by reinforced insulation. Provide reinforced 
insulation between the wire for the input signal and the wires for instrument power supply, source 
of power and loads. 
 
Be sure to provide an appropriate surge control circuit respectively for the following:   
− 
If input/output or signal lines within the building are longer than 30 meters. 
− 
If input/output or signal lines leave the building, regardless the length. 
 
This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage 
connections such as power supply terminals must be enclosed in the instrumentation panel to 
avoid electric shock by operating personnel. 
 
All precautions described in this manual should be taken to avoid damage to the instrument or 
equipment. 
 
All wiring must be in accordance with local codes and regulations. 
 
To prevent instrument damage or failure, protect the power line and the input/output lines from 
high currents with a protection device such as fuse, circuit breaker, etc. 
 
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric 
shock, fire or malfunction. 
 
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock, 
fire or malfunction. 
 
For proper operation of this instrument, provide adequate ventilation for heat dispensation. 
 
Do not connect wires to unused terminals as this will interfere with proper operation of the 
instrument. 
 
Turn off the power supply before cleaning the instrument. 
 
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or 
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument. 
 
To avoid damage to instrument display, do not rub with an abrasive material or push front panel 
with a hard object.
 
NOTICE 
 
This manual assumes that the reader has a fundamental knowledge of the principles of electricity, 
process control, computer technology and communications. 
 
The figures, diagrams and numeric values used in this manual are only for purpose of illustration. 
 
RKC is not responsible for any damage or injury that is caused as a result of using this instrument, 
instrument failure or indirect damage. 
 
RKC is not responsible for any damage and/or injury resulting from the use of instruments made 
by imitating this instrument. 
 
Periodic maintenance is required for safe and proper operation of this instrument. Some 
components have a limited service life, or characteristics that change over time. 
 
Every effort has been made to ensure accuracy of all information contained herein. RKC makes 
no warranty expressed or implied, with respect to the accuracy of the information. The information 
in this manual is subject to change without prior notice. 
 
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, 
processed or retrieved through any mechanical, electronic, optical or other means without prior 
written approval from RKC. 
The Z-COM module joins with functional modules (Z-TIO, Z-DIO modules) and performs PLC 
communication and host communication. The combination of Z-COM module and functional module 
is called an SRZ unit. 
 
SRZ unit
Z-COM module 
Power supply 24 V DC 
Host communication 
Host computer 
Programmable controller 
Z-TIO and Z-DIO modules
PLC communication 
 
1. PARTS DESCRIPTION 
 
Module mainframe
 
 
 
DIP switch 
ON
OFF
1
234
5
6
7
8
NO 
Z-COM module (Right side view)
 
Indication lamp 
FAIL/RUN 
When normal: 
A green lamp is on (RUN) 
[Green or Red] 
Self-diagnostic error: 
A green lamp flashes (FAIL) 
 
Instrument abnormality:  A red lamp is on (FAIL) 
RX1/TX1 
[Green] 
The green lamp is lit when data corresponding to communication 1 
(COM. PORT1/COM. PORT2) is sent or received. 
RX2/TX2 
[Green] 
The green lamp is lit when data corresponding to communication 2 
(COM. PORT3/COM. PORT4) is sent or received. 
 
Communication port (modular connector) and Communication connector 
COM. PORT1 
(Communication 1) 
Used to connecting the Operation panel or Host computer. 
 
  [RS-485 or RS-422A]
COM. PORT2 
(Communication 1) 
The COM. PORT2 is used for the extension of the SRZ unit. 
 [RS-485 
or 
RS-422A]
COM. PORT3 
(Communication 2) 
Used to connecting the programmable controller (PLC), Operation 
panel or Host computer. 
  [RS-485 or RS-422A]
COM. PORT4 
(Communication 2) 
The COM. PORT4 is used for the extension of the SRZ unit. 
 [RS-485 
or 
RS-422A]
Loader 
communication 
connector 
This is a connector to be connected to converter and personal 
computer when loader communication is performed. 
 
Switch 
Address setting 
switch 
Set unit address of SRZ unit with address setting switch. 
DIP switch 
•  Sets communication speed, communication protocol and data bit 
configuration corresponding to each of communication 1 and 
communication 2. 
•  Sets dip switch setting validity/invalidity. 
 
 
 
Base 
 
 
 
 
 
 
 
 
 
 
 
 
2. MOUNTING 
 
 
 
 
 
 
 
2.1 Mounting Cautions 
(1) This instrument is intended to be used under the following environmental conditions. 
(IEC61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2] 
(2)  Use this instrument within the following environment conditions. 
•  Allowable ambient temperature: 
−10 to +50 °C 
•  Allowable ambient humidity:   
5 to 95 % RH 
(Absolute humidity: MAX. W. C 29.3 g/m
3
 dry air at 101.3 kPa) 
•  Installation environment conditions:  Indoor use 
 
Altitude up to 2000 m 
(3)  Avoid the following conditions when selecting the mounting location: 
•  Rapid changes in ambient temperature which may cause condensation. 
•  Corrosive or inflammable gases. 
•  Direct vibration or shock to the mainframe. 
•  Water, oil, chemicals, vapor or steam splashes. 
•  Excessive dust, salt or iron particles. 
•  Excessive induction noise, static electricity, magnetic fields or noise. 
•  Direct air flow from an air conditioner. 
•  Exposure to direct sunlight. 
•  Excessive heat accumulation. 
(4)  Take the following points into consideration when mounting this instrument in the panel. 
•  Ensure at least 50 mm space on top and bottom of the instrument for maintenance and 
environmental reasons. 
•  Do not mount this instrument directly above equipment that generates large amount of heat 
(heaters, transformers, semi-conductor functional devices, large-wattage resistors). 
•  If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or 
the like. However, do not allow cooled air to blow this instrument directly. 
•  In order to improve safety and the immunity to withstand noise, mount this instrument as far 
away as possible from high voltage equipment, power lines, and rotating machinery. 
High voltage equipment: 
Do not mount within the same panel. 
Power lines: 
Separate at least 200 mm. 
Rotating machinery: 
Separate as far as possible. 
•  Be sure the Z-COM module and functional modules (Z-TIO, Z-DIO) are joined when using them. 
 
Top
Bottom
 
(5)  This instrument is Permanently connected to equipment, please take the following points. 
•  A switch or circuit-breaker shall be included in the building installation. 
•  It shall be in close proximity to the equipment and within easy reach of the operator. 
•  It shall be marked as the disconnecting device for the equipment. 
 
2.2 Joining Each Module 
Before joining the Z-COM module and functional modules, use the DIP 
switches to make the communication settings. For the setting procedure, see 
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-E ).
 
 
The maximum number of functional modules (Z-TIO-A/B, Z-DIO) described in the following can be 
joined per Z-COM module. For details on joining functional modules with the Z-COM module, see 
the Z-TIO INSTRUCTION MANUAL (IMS01T01-E ).
 
•  When joining functional modules of the same type: 
Up to 16 modules
 
•  When joining functional modules of two or more different types:  Up to 31 modules 
(However, the maximum joinable number of functional modules of the same type is 16.) 
  [Example]  When the Z-TIO-A/B and Z-DIO modules are joined   
 
SRZ unit
16 Z-TIO-A/B modules
Z-COM module
Functional modules: Up to 31 modules 
15 Z-DIO modules
 
 
When the number of correspondence channels is specified using the model code, only the 
amount of data corresponding to the specified number of channels can be sent or received 
(PLC communication only). 
The number of the 
correspondence 
channels 
Z-TIO-A/B module 
Z-DIO module 
64 channels 
64 channels 
(However, up to 16 modules)
128 channels 
(Up to 16 modules) 
48 channels 
48 channels 
(However, up to 16 modules)
96 channels 
(Up to 12 modules) 
32 channels 
32 channels 
64 channels 
(Up to 8 modules) 
16 channels 
16 channels 
32 channels 
(Up to 4 modules) 
2.3 Dimensions 
 
76.9 30 
6.7
100
 
(Unit: mm) 
 
 
 Space required between each 
 Depth for communication cables mount   
module vertically   
  type module 
When the module is mounted on the panel, 
Space for communication cables must be   
allow a minimum of 50 mm at the top and   
considered when installing. 
bottom of the module to attach the module 
to the mainframe. 
 
76.9
(Unit: mm) 
Communication 
cables 
Approx. 50
50 mm or more
 
 
 
Procedure for mounting or removing 
The procedure for mounting or removing the Z-COM module is the same as that of the function 
module (Z-TIO or Z-DIO). Both DIN rail mounting and screw mounting are available. 
For details on module mounting or removing, see the Z-TIO INSTRUCTION MANUAL 
(IMS01T01-E )
 
 
3. WIRING
 
 
 
 
 
 
 
3.1 Wiring Cautions 
•  To avoid noise induction, keep communication signal wire away from instrument power line, load 
lines and power lines of other electric equipment. 
•  If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter. 
−  Shorten the distance between the twisted power supply wire pitches to achieve the most 
effective noise reduction. 
−  Always install the noise filter on a grounded panel. Minimize the wiring distance between the 
noise filter output and the instrument power supply terminals to achieve the most effective 
noise reduction. 
−  Do not connect fuses or switches to the noise filter output wiring as this will reduce the 
effectiveness of the noise filter. 
•  Power supply wiring must be twisted and have a low voltage drop. 
•  For an instrument with 24 V power supply, supply power from a SELV circuit. 
•  A suitable power supply should be considered in the end-use equipment. 
The power supply must be in compliance with a limited-energy circuits (maximum available 
current of 8 A). 
•  Supply the power to only one of the joined modules. When power is supplied to any one of the 
joined modules, all of the joined modules will receive power. 
•  Select the power capacity which is appropriate for the total power consumption of all joined 
modules and the initial current surge when the power is turned on. 
Power consumption (at maximum load): 
30 mA max. (at 24 V DC) 
 
Rush current: 10 A or less 
•  When connecting the wiring to the power supply terminals on the base, use the specified 
solderless terminals. Only these specified solderless terminals can be used due to the insulation 
between the terminals. 
Screw Size: M3 
× 7 (with 5.8 × 5.8 square washer) 
Recommended tightening torque: 0.4 N・m (4 kgf・cm) 
Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm
Specified solderless terminal: 
Manufactured by
 
J.S.T MFG CO., LTD. 
Circular terminal with isolation
 
V1.25
−MS3 
(M3 screw, width 5.5 mm, hole diameter 3.2 mm) 
 
3.2 Terminal Configuration 
 
Base 
 
 
 
3 4  5 
Supply the power to only one of the
joined modules. 
When power is supplied to any one of the
joined modules, all of the joined modules
will receive power. 
Terminals 3, 4 and 5 (Usage is prohibited.) 
1
2
24 V DC
+
Power supply 
terminals 
 
Z-COM Installation Manual (This manual) ........................................................................ 1 
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-E )....................... 1 
Z-COM PLC Communication Data List (IMS01T15-E )................................................. 1 
Z-COM Host Communication Quick Instruction Manual (IMS01T09-E ) ...................... 1 
Joint connector cover (KSRZ-517A).................................................................................. 2 
Power terminal cover (KSRZ-518A).................................................................................. 1 
All Rights Reserved, Copyright 
 2006, RKC INSTRUMENT INC. 
Z-COM 
Installation 
Manual
 
Communication 
Extension Module
 
1 2 
3 4 5 
Joint connector 
Used to mechanically and 
electrically connect   
each module. 
Power supply terminals 
These are terminals to supply 
power to the Z-COM module 
or joined function modules. 
Terminal 3, 4 and 5   
These terminals cannot be 
used for the Z-COM module. 
(Usage is prohibited.) 
Mounting holes (M3 screw) 
Holes for screws to fix the base 
to a panel, etc. 
Customer must provide the M3 
screws. 
Mounting bracket 
Used to fix the module on   
DIN rails and also to fix   
each module joined together. 
 
 
 
To prevent electric shock or instrument failure, always turn off the 
power before mounting or removing the instrument. 
!
WARNING
 
 
 
 
To prevent electric shock or instrument failure, do not turn on the 
power until all the wiring is completed. 
!
 
WARNING
 
 
 
An external protection device must be installed if failure of this instrument 
could result in damage to the instrument, equipment or injury to personnel. 
 
All wiring must be completed before power is turned on to prevent electric 
shock, fire or damage to instrument and equipment. 
 
This instrument must be used in accordance with the specifications to 
prevent fire or damage to instrument and equipment. 
 
This instrument is not intended for use in locations subject to flammable or 
explosive gases. 
 
Do not touch high-voltage connections such as power supply terminals, 
etc. to avoid electric shock. 
 
RKC is not responsible if this instrument is repaired, modified or 
disassembled by other than factory-approved personnel. Malfunction can 
occur and warranty is void under these conditions. 
!
 
WARNING 
CAUTION 
φ 5.5 MAX
φ 3.2 MIN
9.0 mm
5.6 mm
φ 3.2
Loader communication
connector
COM. PORT1
COM. PORT2
Indication lamp (RX1/TX1)
Indication lamp (RX2/TX2)
Communication 1 
Indication lamp (FAIL/RUN)
Address setting switch
COM. PORT3
COM. PORT4
Communication 2 
Communication port
Communication port