IntelliTouch ScreenLogic User’s Guide
Setup Solar Equipment and Heat pump option
Solar equipment is configured in the “Configure Other Equipment (Step 3 of 5)” dialog, page 43.
To configure solar equipment:
1. Start the ScreenLogic Configurator and tap Configure IntelliTouch.
2. Tap Next on the General Setting page and on the Setup Circuits page. The Configure Other Equipment
(Step 3 of 5) page is displayed. For i10+3D Dual Equipment, tap the Solar present check box for each
body of water with solar heating.
3. Tap the Solar present check box to enable solar heating. Valve A: USED BY SOLAR is displayed indicating
that valve A is assigned for solar operations.
If your heat pump is being used instead of solar panels, tap the Solar is a heat pump check box,
then assign a circuit to the valve in the “Circuit Assigned to Valve” box.
Note: If solar heat source is enabled (Solar present check box selected) then the Valve A
actuator will be dedicated to the solar valve actuator. Setting the system to Heat pump (Solar is
a heat pump) will free Valve A for use on other valves.
4. Tap Finish when done.
Set a Cool-Down Cycle for the Heater
To activate the pump during a heater cool-down:
1. Start the ScreenLogic Configurator and tap Configure IntelliTouch.
2. Tap Next on the General Setting page and on the Setup Circuits page. The Configure Other Equipment
(Step 3 of 5) page is displayed.
3. Tap the Pump on during heater cool-down check box under the “Delays” option.
4. Tap Finish when done.
Note: Pentair heaters do not require this feature.