Справочник Пользователя для NotaTech 8000SeriesI/O

Скачать
Страница из 28
0
Contact:
®
NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD  21117
T: 410.753.8300
Toll Free: 800.253.3842
www.novatechweb.com
.  8 single-ended input channels 
 .  Non-incendive field circuits 
 .  1–5 V inputs  open circuit and short circuit detection 
 .  24 V dc bussed field power required 
Module Specifications  
Inputs
 
Number of channels ...............................................8, single-ended 
Nominal signal range (span) ................................................1 to 5 V 
Full signal range ...........................................................0.19 to 5.64 V 
Input impedance.........................................................................2 MΩ 
Out of range alarm 
     Lower threshold ................................................................< 0.19 V
     Upper threshold ................................................................> 5.64 V
Accuracy (over temp range) ...................................± 0.1% of span
Resolution ..................................................................................16 bits
Repeatability ................................................................0.05% of span
Isolation (any channel to Railbus) .....................................100 V ac
     (between channels)................................................................none
Configurable Parameters
Input filter time constant .................................user defined value
Input dead zone .................................................user defined value
Drive on failsafe............................. disabled /upscale /downscale
Channel status.......................................................... active /inactive
Response Time
Signal change to availability on Railbus .................27 ms (max.) 
Safety
FM non-incendive field wiring parameters (each channel) 
..................V
oc
 = 28.7 V; I
sc
 = 33 mA; C
a
 = 0.17 µF; L
a
 = 11.0 mH
Power Supplies
Railbus (12V) current .....................100 mA (typ.)/150 mA (max.)
Bussed Field Power ...................... 60 mA (max.) at 24 Vdc ± 10%
NT
-8119-VI-05
Image Description
8-channel Analog Input 
1–5 V
Mechanical
Module Key Code ............................................................A1
Module width .............................................................42 mm
Weight..........................................................................200 g
Field Terminals 
Field Wiring
Recommended 
Field Terminal
Compatible 
Field Terminal
General Purpose
NT-8615-FT-4W 
4-wire transmitter
-
Class 1, Div 2 
or Zone 2 hazard-
ous area
NT-8615-FT-4W  
4-wire transmitter
-
NovaTech 8000 Series I/O Family
3AFE
OR
/THER
CHANNELS

"USSED
2AILBUS
-58
!$
M0
#HANNEL
n6
$#
Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks 
are properties of their respective owners. NovaTech is a registered 
trademark  of  NovaTech,  LLC.  The  information  in  this  literature  is 
subject to change without notice and is not to be construed as a 
warranty.  DS_8119_0607